General
Transmission rate
Interfaces
Cable length
Power supply
Current consumption
Power loss
Backup battery (optional) for message memory
and hardware clock
Clock
Permitted ambient conditions
Construction
Degree of protection
SINAUT ST7 Station control system - System Manual
System Manual, 05/2007, C79000-G8976-C178-06
RS-232/RS-485
Ethernet
Communication port,
electrical
Connector for power supply
Slot for exchangeable media
RS-232
RS-485
RJ-45
From backplane bus
From 24 V DC
Battery type
Voltage / capacity
Current consumption during backup
Leakage current
Hardware clock (real-time clock)
Buffered
Deviation per day
Operating temperature
Transport/storage temperature
Relative humidity
Module format
Dimensions (W x H x D) in mm
Weight
Introduction to the SINAUT ST7 system
2.3 SINAUT TIM communication modules
50 to 38,400 bps
10/100 Mbps autosensing
- 9-pin D-sub male, RS-232,
can be switched over to RS-485;
- RJ-45 (10/100 Mbps; TP)
1 x 2-pin plug-in terminal strip
C-PLUG (optional)
max. 6 m
max. 30 m
max. 10 m
24 V DC; min. 20.4 V; max. 28.8 V
maximum 200 mA
typically 150 mA, max. 170 mA
typically 4.6 W
Lithium battery 6ES7 971-0BA00
Type Tadiran SL-306, cell type AA
3.6 V nominal / 2.3 Ah
typically 100 μA, max. 160 μA
typically 15 μA
Yes
yes (with backup battery)
max. 4 s
0 °C through +60 °C
-40 °C through +70 °C
Max. 95 % at +25 °C
Compact module for S7-300, double width
80 x 125 x 120
Approx. 400 g