Modem reset
If the configuration of the modem is unclear, you can reset to the factory default settings.
When you reset the modem, all 16 standard profiles are reset to the default setting.
Procedure:
1. Power supply OFF
2. Set switch SW2.7 to ON
3. Turn the power supply ON and then wait at least 10 seconds until the DCD LED lights up.
4. Power supply OFF, set switch SW2.7 to OFF
5. Select the basic setting and standard profile and turn the power supply ON
Figure 6-32
Default settings of the DIL switches SW1 and SW2
When it ships, the modem has the following default settings:
● Metering pulse filter 16 kHz
● Loop power section activated
● Standard dialing profile 0: AT mode
● Data format 11 bits (8E1)
● Tone dialing
● Loudspeaker OFF
● Line adjustment Zr
When shipped, the switches are set as shown in the following figure.
Figure 6-33
SINAUT ST7 Station control system - System Manual
System Manual, 05/2007, C79000-G8976-C178-06
Setting the DIL switch for a modem reset
Default settings of the DIL switches SW1 and SW2
Installing and putting a SINAUT modem into operation
6.6 Analog dial-up modem MD3
283