Interlogix ATS125 Series Programming Manual page 52

Fourdoor/four-lift dgp
Hide thumbs Also See for ATS125 Series:
Table of Contents

Advertisement

On Delay: Activates after the programmed time period unless the result of the
logic equation is no longer valid.
Off Delay: Follows the result of the logic equation, but remains active for the
time programmed after the result of the logic equation is no longer active.
Latched: Activates on any of the first three macro inputs in the logic equation
and is only reset by the fourth macro input. Any programmed AND / OR
function is not used).
How to program
Press one of these keypad buttons to:
[MENU*]: Display a new output function.
0: Leave the menu
? [ENTER]: Enter the event flag number. The flag activates if the result of the
logic equation is true.
[ENTER]: Save the displayed function and move to the next display.
Time
M X, E0 On Pulse 0 Sec
*-Chg,Event:
The time period (1 to 255 seconds or minutes) that is used when any of the timed
macro output functions are selected (pulse, on timed, on delay or off delay).
When programming 1 to 4 minute periods, program the value in seconds to
improve the accuracy, for example, 60, 120, 180, or 240 seconds.
Logic equation
MX,E0 OR E0 OR E0 OR EO
1st Event:
Program up to four macro inputs (for example, ATS125x event flag numbers).
The logic connecting the four inputs may be the AND or OR function. A NAND or
NOR function can be achieved by inverting the logic of the particular input.
When all conditions of the logic equation have been met, the result is true, and
the event programmed in the previous steps will be activated (depending on any
timing function programmed).
Note:
Any macro logic inputs not used MUST be left as an OR function.
How to program
Press one of these keypad buttons to:
? [ENTER]: Enter and display new event flag number. Enter the same number
twice to invert the macro input. Before calculating the result of the macro logic
equation, the input is inverted. An inverted input is recognized by the
exclamation mark (!) preceding the "E".
[MENU*]: Toggle between OR or AND function.
[ENTER]: Save the displayed details and move to the next display.
46
ATS125x/1260 Four-Door/Four-Lift DGP Programming Guide

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ats1260

Table of Contents