Shunt until door has closed
XX, NO Shunt Until Door Closed
*-Change
Set the shunt period to, until the door has closed.
Yes: Shunt the defined zones as programmed in hardware options "shunt
zones" until the door is closed. When the door is opened and the shunt is not
active the zone will generate an alarm.
No: Shunt timer will be used.
Cancel shunt time after door closed
XX,NO Cancel Shunt After Door Secures
*-Change
For security reasons, it may be required to limit the shunt period as much as
possible.
Yes: Shunt the programmed zones until the door has closed. Opening the
door again within the shunt time is not possible, as this will generate an alarm
(there is always a debounce time of approx. 2 seconds).
No: Shunt timer will be used.
Low security timezone
XX,Low Security Timezone Disabled
*-Dis, TZ:
Enter a timezone number. When the timezone is valid, only a valid card or PIN is
required to open the door. When the timezone is not valid and "Card and PIN
Reader" is set to YES, a valid card and PIN must be entered to open the door.
Note:
Timezones are programmed in the Advisor Master in menu 13. Only
timezones 0 to 24 may be entered. Timezone 0 means always.
IN reader requires card and PIN
XX, NO - In Reader Card & PIN
*-Change
Specify what method is required to open the door from the IN reader. This is
programmed separately for the IN and OUT readers.
Yes: Unlock the door by presenting a valid card to the reader and entering a
PIN on the reader's keypad.
No: Unlock the door by presenting a valid card to the reader or a valid PIN on
the reader's keypad.
18
ATS125x/1260 Four-Door/Four-Lift DGP Programming Guide