Interlogix ATS125 Series Programming Manual page 34

Fourdoor/four-lift dgp
Hide thumbs Also See for ATS125 Series:
Table of Contents

Advertisement

Zone holds door unlocked
XX, NO - Zone Holds Door Unlocked
*-Change
This record determines when the door will re-lock using the re-lock delay.
Yes: The door lock will not re-lock until the door is closed. This is used where
the lock mechanism, when locked, will stop the door closing.
No: The door lock will re-lock (after the unlock time has expired, etc.)
regardless of the door being open or closed.
Door unlocked until door open
XX, NO - Door Unlocked Until Door Opens
*-Change
For security reasons, it is possible for the door to re-lock at the moment it opens.
The door relay will be de-activated after the door is opened. This option will
override the unlock time. The door will stay unlocked until opened.
Yes: The door relay will stay activated (initialised by a valid card or PIN) until
the door zone has switched back to normal (the door has closed).
No: The door relay will perform standard operation.
Unlocked timezone
XX, Unlock Timezone Disabled
*-Dis, TZ:
The programmed timezone will automatically unlock the door for the programmed
time periods. Free access is allowed when the timezone is valid.
Note:
Timezones are programmed in the Advisor Master in menu 13. Only
Timezones 0 to 24 can be entered.
Unlocked timezone after entry
XX, NO - Unlock Timezone After Entry
*-Change
Select if the override takes effect immediately the timezone commences or after
a user has entered.
Yes: Before the timezone will unlock the door, a user needs to enter the area.
No: Automatic unlock will start at the timezones start time.
28
ATS125x/1260 Four-Door/Four-Lift DGP Programming Guide

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ats1260

Table of Contents