4.6 Connection of Scan I/O card

(1) External power supply (DCIN)
24VDC is required for the HR347/HR357 card operation. Prepare a stabilized power supply that satisfies the
following specifications.
Output: 24VDC±5%
Ripple: ±5%(P-P)
Rated output current: 2.5A
* The rated output current is the value when using 60mA × 32 points for the machine output.
Prepare a power supply that satisfies the 24VDC output's total output current and control current (0.5A).
25
1
A
(Scan DI/DO : 64/64)
B
CF35
CF31
(DO : 32)
20
1
HR357
(2) Connecting the remote I/O communication cable (RIO3A/B)
(a) Connection of the RIO3A connector
Connect the RIO3A to the RIO1 connector of the control unit or the RIO3 of the operation panel I/O unit.
(b) Connection of the RIO3B connector
Multiple remote I/O units can be used, as long as the total No. of occupied stations connected with serial links
is less than eight. (Refer to "Connection: Connection of Remote I/O Unit" for details.) HR357 occupies three
stations, so the remote I/O units can be connected to the RIO3B in combinations of 5 stations or less. Connect
a terminator to the RIO3B when it is not connected to any device.
25
A
(Scan DI/DO : 64/64)
B
CF35
CF31
(DO : 32)
20
ISP
DIO
SCAN2 SCAN1
8
1
DCIN
RIO3
DCIN
B
A
CF33
(DO : 32)
20
1
Control unit
RIO1
FCUA-R211
ISP
1
SCAN2
SCAN1
DIO
8
1
RIO3
DCIN
B
B
A
R IO3
CF33
(DO : 32)
20
1
1
HR 357
M70V Series Connection Manual
4.6 Connection of Scan I/O card
F070
cable
24VDC
0V(RG)
25
ISP
1
8
1
A
(Scan DI/DO : 64/64)
B
CF35
RIO3
CF31
(DO : 32)
(DO : 32)
20
20
1
HR357
FCUA-R211
To the next remote I/O unit
FC UA-DX1xx
Terminator
 R - TM
DIO
SCAN2 SCAN1
RIO3
DCIN
B
A
A
X
1
2
3
CF33
1
147