Chapter 4: Menu reference
Select the appropriate macro and click Browse "..." to open the Macro form.
On the Macro form, click Remove to remove the macro data.
The following settings are available.
Output function
The result of the macro logic and the macro output function will trigger an event
flag. The macro output may have timing functions.
Disabled: This macro logic program is disabled.
Non-timed: Follows the result of the logic equation only. If a macro input for
this macro changes, the logic equation will be calculated again.
On pulse (1 to 255) seconds: Activates for the programmed time or the active
period of the logic result, whichever is the shortest.
On pulse (1 to 255) minutes: Activates for the programmed time or the active
period of the logic result, whichever is the shortest.
On timed (1 to 255) seconds: Activates for the programmed time regardless
of the macro inputs changing.
On timed (1 to 255) minutes: Activates for the programmed time regardless of
the macro inputs changing.
On delay (1 to 255) seconds: Activates after the programmed time period
unless the result of the logic equation is no longer valid.
On delay (1 to 255) minutes: Activates after the programmed time period
unless the result of the logic equation is no longer valid.
Off delay (1 to 255) seconds: Follows the result of the logic equation, but
remains active for the time programmed after the result of the logic equation
is no longer active.
Off delay (1 to 255) minutes: Follows the result of the logic equation, but
remains active for the time programmed after the result of the logic equation
is no longer active.
Latched: Activates on any of the first three macro inputs in the logic equation
and is only reset by the fourth macro input (any programmed AND / OR
function is not used).
Duration
Enter the time period (1 to 255 seconds or minutes) that is used when any of the
timed macro output functions are selected (On pulse, On timed, On delay, or Off
delay).
When
Enables programming of up to four logic inputs, which can be a wide variety of
conditions such as Door open too long, each corresponding to a specific DGP
event. For each logic input, select the logic input type, then select the specific