Chapter 1: Installation

Output fusing and user current draw

The current draw on the door controller for all user devices must not exceed 3 A.
This value excludes battery charging and standalone board current.
The door controller will shut down if this is exceeded.
In some environments, further restrictions on user current apply as detailed in
"Operating temperature" on page 39.
On-board fuses provide over-current protection for devices as described in
Table 4 below. The numbers in the Item number column refer to items in
Figure 12 on page 13.
Table 4: Maximum current draw per output
Device
Auxiliary power
Siren output
Four on-board relays
Active relay coil
Relay expander
Bus 1
Bus 2
Lock power 1
Lock power 2
Consider the maximum current draw from the devices above when calculating
the total user current draw.
38
Item number
Maximum current draw
6
0.81 A total
7
1.25 A RMS
10
1.7 A each (when using lock power 12 V
and 0 V)
10
55 mA
13
0.5 A
18, 20, and 21
1.0 A total
19
0.5 A
32
1.9 A
22
1.25 A
CDC4 Door Controller Installation and Programming Manual