Omron CK3W-GC 00 Series Hardware User Manual page 52

Programmable multi-axis controller
Hide thumbs Also See for CK3W-GC 00 Series:
Table of Contents

Advertisement

3 Configuration Units
Terminal Arrangement
Terminal block
Abbreviation Signal name
+
-
Output Status
In normal operation, it is ON, and at other times it is OFF.
When unit power is OFF
During normal operation
When hardware watchdog error occurs OFF
When software watchdog error occurs
Output Specifications
Rated voltage
Operating load voltage range
Maximum load current
Leakage current
Residual voltage
ON/OFF response time
Isolation method
Circuit configuration
3-8
WDTOUT+
WDTOUT-
Status
Output
OFF
ON
OFF
Item
CK3M-series Programmable Multi-Axis Controller User's Manual Hardware (O036)
Specification
24 VDC
20.4 to 26.4 VDC
0.1 A
0.1 mA max.
1.5 V max.
10 ms max./10 ms max.
Photocoupler isolation
Internal
circuit
WDTOUT+
WDTOUT-

Advertisement

Table of Contents
loading