Power consumption
Dimensions (height × depth × width)
Weight
*1.
Differential input and single-ended input can be mixed in a Unit.
3-5-2
Part Names and Functions
(A)
(F)
Letter
A
Slider
B
Power supply status indicator Shows the power supply status.
C
Terminal block
D
Unit connector
E
DIN Track mounting hook
F
Address switch
CK3M-series Programmable Multi-Axis Controller User's Manual Hardware (O036)
(B)
(C)
(D)
(E)
Name
Holds the Units together.
Connects the analog input.
Connector that connects to the Unit.
Used to mount the Unit to a DIN Track.
Sets the Gate3 Index.
For single-ended input
Input 0+ to 7+
Input 0- to 7-
AGND
FG
FG
•
If any of Input 0- to Input 7- is single ended input, apply a
short-circuit between the input and AGND.
•
Use a shielded cable and ground at both ends of the ca-
ble.
CK3W-AD3100: 5 V 0.9 W max., 24 V 2.0 W max.
CK3W-AD2100: 5 V 0.9 W max., 24 V 1.4 W max.
90(H)/80(D)/31.6(W)
CK3W-AD3100: 140 g max.
CK3W-AD2100: 120 g max.
Function
3 Configuration Units
3-55
3