Operation Indicators; Address Switch Setting - Omron CK3W-GC 00 Series Hardware User Manual

Programmable multi-axis controller
Hide thumbs Also See for CK3W-GC 00 Series:
Table of Contents

Advertisement

3 Configuration Units
3-5-3

Operation Indicators

The LED indicator shows the unit operating status of the Analog Input Unit.
The operating statuses corresponding to the colors and statuses of the indicators are shown below.
Indicator name Color Status
PWR
3-5-4

Address Switch Setting

This Unit is equipped with an IC that has the same interface as a PMAC3 style DSPGate3 IC.
Refer to the Power PMAC User's Manual (Cat. No. O014) for the PMAC3 style DSPGate3 IC.
The address switch settings are used to set the Gate3 Index.
The setting range is from 0 to F. (Factory setting: 0)
Address switch setting
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
For example, if the address switch setting is 0, the Gate3 Index becomes 0.
In this case, this Unit is accessed with a Gate3[0] data structure.
Make sure that the address switch settings of Units do not overlap.
If they overlap, the Sys.Status register CK3WConfigErr becomes 7.
Refer to 6-4 Sys.Status Register on page 6-10 for Sys.Status.
One CK3W Unit in the system supplies servo clock and phase clock signals to all the other Units.
The supply-source CK3W Unit must be installed to the CPU Rack.
3-56
Description
Green
ON
Power is supplied.
OFF
Power is not being supplied.
Power PMAC
"Gate3" Index
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
CK3M-series Programmable Multi-Axis Controller User's Manual Hardware (O036)