Menus And Submenus - Johnson Controls TEC3010 Installation Instructions Manual

Tec3000 series wireless single- or two-stage economizer thermostat controllers
Hide thumbs Also See for TEC3010:
Table of Contents

Advertisement

Menus and Submenus

In the following table, the * indicates that the menus depend on your configuration.
Table 10: Menus and Submenus (Part 1 of 9)
Level 1
Level 2
(LCD Screen Name)
Setpoints
Occ Cooling Setpoint
Occ Heating Setpoint
Unocc Cooling Setpoint
Unocc Heating Setpoint
Stby Cooling Setpoint
Stby Heating Setpoint
Occ Setpoint Select
Heat Cool Setpoint Mode
Max Heating Setpoint*
Min Heating Setpoint*
Max Cooling Setpoint*
Min Cooling Setpoint*
Max Setpoint*
Min Setpoint*
TEC3000 Series Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
Level 3
Available Values
(Default Values)
72°F (22°C)
55 to 85°F (13 to 30°C)
68°F (20°C)
55 to 85°F (13 to 30°C)
80ºF (27°C)
55 to 85°F (13 to 30°C)
60°F (15°C)
55 to 85°F (13 to 30°C)
74°F (23°C)
55 to 85°F (13 to 30°C)
66°F (19°C)
55 to 85°F (13 to 30°C)
Setpoint Offset
Min and Max Setpoint or Setpoint Offset
Individual
Common Setpoint or Individual Setpoint
Setpoints
68°F (20°C)
The range (in degrees) from the Min
Heating Setpoint temperature to the Min
Cooling Setpoint temperature minus 1°F
(0.55°C). (The cooling temperature
always needs to be 1°F [0.55°C] above
the heating temperature.)
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select ==
Min and Max Setpoint.
60°F (15°C)
45°F (7.22°C) to Max Heating Setpoint
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select ==
Min and Max Setpoint.
80ºF (27°C)
Min Cooling Setpoint to 100°F (37.77°C)
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select ==
Min and Max Setpoint.
72°F (22°C)
The range (in degrees) from the Max
Heating Setpoint temperature plus
1°F (0.55°C) to the Max Cooling Setpoint
temperature.
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select ==
Min and Max Setpoint.
80ºF (27°C)
Min Setpoint to 100°F (37.77°C)
*These values only appear when Heat
Cool Setpoint Mode == Common
Setpoint and Occ Setpoint Select == Min
and Max Setpoint.
60°F (15°C)
45°F (7.22°C) to Max Setpoint
*These values only appear when Heat
Cool Setpoint Mode == Common
Setpoint and Occ Setpoint Select == Min
and Max Setpoint.
29