Table 10: Menus and Submenus (Part 6 of 9)
Level 1
Level 2
(LCD Screen Name)
Equipment Setup
General
Number of Compressor
Lead/Lag Equalize Runtime
Number of Heating Stages*
Compressor Min On Time
Compressor Min Off Time
Heating Min On Time
Heating Min Off Time
Supp Min On Time
Supp Min Off Time
Cooling Lockout Temp
Heating Lockout Temp
Unoccupied Off Delay
Economizer*
Economizer Installed
Economizer Min Pos*
Closed Voltage*
Open Voltage*
Dry Bulb Setpoint
Outdoor Enthalpy Setpoint
Heat Pump*
Heat Pump Supported
Supp Heating Installed*
Comp Low Lockout Temp*
Supp High OA Lockout Temp*
Rev Valve Polarity*
TEC3000 Series Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
Level 3
Available Values
(Default Values)
One-Stage
Not Used, One-Stage, Two-Stage
No
Yes or No
Two-Stage
Not Used, One-Stage, Two-Stage
* Heat pump unit,
Heat Pump supported = False
180 seconds
0 to 360 seconds
180 seconds
0 to 360 seconds
120 seconds
0 to 360 seconds
* Heat pump unit,
Heat Pump supported = False
120 seconds
0 to 360 seconds
* Heat pump unit
120 seconds
0 to 360 seconds
* Heat pump unit,
Supp Heating Installed = True
120 seconds
0 to 360 seconds
* Heat pump unit,
Supp Heating Installed = True
40°F (4°C)
0 to 100°F (-18 to 38°C)
80°F (27°C)
0 to 100°F (-18 to 38°C)
10 minutes
0 to 10 minutes
False
True or False
20%
0 to 100%
* Economizer = True
2 VDC
0 to 10 VDC
* Economizer = True
10 VDC
0 to 10 VDC
* Economizer = True
68°F (20°C)
0 to 100°F (-18 to 38°C)
* Economizer = True
27 Btu/lb
0 to 100 Btu/lb dry air
* Economizer = True
False
True or False
True
True or False
* Heat Pump supported = True
32°F (0°C)
-20 to 100°F (-29 to 38°C)
* Supp Heating Installed = True
50°F (10°C)
-20 to 100°F (-29 to 38°C)
* Supp Heating Installed = True
Normally Heat
Normally Heat, Normally Cool
* Heat Pump supported = True
34
1