Technical Specifications - Johnson Controls TEC3010 Installation Instructions Manual

Tec3000 series wireless single- or two-stage economizer thermostat controllers
Hide thumbs Also See for TEC3010:
Table of Contents

Advertisement

Technical Specifications

TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers
Power Requirements
USB Port Power Rating
Relay Contact Rating
Binary Inputs
Analog Inputs
Temperature Sensor Type
Wire Size
MS/TP Network Guidelines
Wireless Band
Transmission Power
Transmission Range
Temperature
Backlit Display
Range
Heating Control
Cooling Control
Accuracy
Temperature
Minimum Deadband
Occupancy Sensor Motion
Detection (Occupancy Sensing
Models)
Ambient
Operating
Conditions
Storage
Compliance
BACnet
International
United States
Canada
Australia and
New Zealand
Shipping
Models without
Weight
Occupancy
Sensor
Models with
Occupancy
Sensor
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or
misuse of its products.
TEC3000 Series Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
19 to 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal, Class 2 or
safety extra-low voltage (SELV)
120 to 250 mA current draw supported
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush, Class 2 or SELV
Voltage free contacts across terminal COM to terminals BI1 or BI2
Nickel, platinum, A99B, 2.25k ohm NTC, 10k ohm NTC, 10k ohm NTC Type 3 across
terminal COM to terminals R SEN
Local 1k ohm platinum sensor
18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm diameter) recommended
Up to 100 devices maximum for each Network Automation Engine (NAE)
Direct-sequence spread-spectrum 2.4 GHz ISM bands
10 mW maximum
50 ft (15.2 m) recommended indoor
250 ft (76.2 m) line of sight, maximum
-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° increments
40.0°F/4.5°C to 90.0°F/32.0°C
54.0°F/12.0°C to 100.0°F/38.0°C
±0.9F°/±0.5C° at 70.0°F/21.0°C typical calibrated
2F°/1C° between heating and cooling
Minimum of 94 angular degrees up to a distance of 15 ft (4.6 m);
based on a clear line of sight
32 to 122°F (0 to 50°C); 95% RH maximum, noncondensing
-22 to 122°F (-30 to 50°C); 95% RH maximum, noncondensing
BACnet Testing Laboratories™ (BTL) 135-2001 Listed BACnet Application Specific
Controller (B-ASC)
UL Listed, File E27734, CCN XAPX, Under UL60730
Transmission complies with FCC Part 15.247 regulations for low power
unlicensed transmitters; transmitter identification FCC: OEJ-WRZRADIO
UL Listed, File E27734, CCN XAPX7 Under E60730
Industry Canada (IC) RSS-210;
Transmitter identification ZFR1810-1: IC: 279A-WRZRADIO
RCM Mark, Australia/NZ Emissions Compliant
0.75 lb (0.34 kg)
0.77 lb (0.35 kg)
45

Advertisement

Table of Contents
loading

Table of Contents