The Fan Override icon on the home screen is dependent on the fan type. The following options are provided for
single-speed fans:
On—Overrides the fan to be continuously on
Auto—Follows the behavior set as Fan Mode
Quiet—Follows the behavior set as Auto Mode. The Quiet option has no effect on the RTU/heat pump
equipment as only a single-speed fan is supported.
To set the Fan Mode:
1. Press the Menu icon.
2. Press Control Setup.
3. Press General.
4. Press Fan Mode and select On, Auto, or Smart.
5. Press
to save and

Configuring the Zone Space or Equipment Size

With non-binary outputs, the TEC3000 is configured by default to have a slower temperature response for larger
zones with normal-sized equipment. In installations with small zones and oversized equipment, set the Equipment
Size parameter to Oversized.
To set the Equipment Size parameter:
1. Press the Menu icon.
2. Press Control Setup.
3. Press Tuning.
4. Use the up and down arrows to navigate to Equipment Size.
5. Press Equipment Setup and select Oversized.
6. Press
to save and

Temperature Setpoints

The thermostat controller provides a flexible setpoint configuration to give power to the building owner while being
easy to use by the occupant. The TEC includes six temperature setpoints in addition to a simple up/down offset
adjustment on the home screen for the occupant. The six temperature setpoints are Cooling and Heating setpoints
for Occupied, Unoccupied, and Standby modes. To set these setpoints:
1. Press the Menu icon.
2. Press Setpoints.
3. Select the setpoint to adjust.
4. Press
to save and
Note: The TEC enforces a 2-degree deadband between heating and cooling setpoints. If a setpoint is set in a way
that violates this standard (for example, cooling setpoint is set to 70 with a heating setpoint already set to 70), the
opposing setpoint is modified to comply with this deadband (in the previous example, the heating setpoint would
automatically change to 68).