Table 10: Menus and Submenus (Part 3 of 9)
Level 1
Level 2
(LCD Screen Name)
Control Setup
Aux Mode
(Cont)
Load Shed Rate Limit
Load Shed Adjust
Fan Alarm Delay
Fan Alarm Action (when Fan Alarm
Delay is greater than 0)
Fan Alarm Reset (when Fan Alarm
Delay is greater than 0)
Fan Runtime Limit
Fan Runtime Reset (when Fan
Runtime Limit is greater than 0)
Supply Air Temperature Alarm Offset
Supply Air Temperature Alarm Delay
(when Supply Air Temp Alarm Offset
is greater than 0)
Inputs
BI1 Config
BI2 Config
Supply Temp Sensor
Supply Temp Offset
Zone Temp Sensor
Zone Temp Offset
OA Temp Offset
OA Temp Sensor
Reset Sensors
Tuning
Temp Control Setup
Reset PID Tuning*
TEC3000 Series Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
Level 3
Available Values
(Default Values)
Not Used
Not Used, Occupied NO, Occupied NC,
Occupied Fan NO, Occupied Fan NC,
On, Off
0.066°F
0 to 1°F (0 to 0.5°C)
4°F
0 to 8°F (0 to 4°C)
0 seconds
0 to 300 seconds
Enable
Enable or Shutdown
No
Yes or No
0 hours
0 to 9,000 hours
No
Yes or No
0°F
0 to 10°F (0 to 5.5°C)
300 seconds
300 to 3,600 seconds
Disabled
Disabled, Open Window, Open Door, Fan
Lock, Service, Dirty Filter, Motion NC,
Motion NO, Temp Occ, Occupancy
Disabled
Disabled, Open Window, Open Door, Fan
Lock, Service, Dirty Filter, Motion NC,
Motion NO, Temp Occ, Occupancy
Nickel
Nickel, Platinum, A99B, 2.25k ohm
negative temperature coefficient (NTC),
10k ohm NTC, 10k ohm NTC Type 3
0
-5 to 5 (°F or °C based on Units setting
under Display Settings menu)
* Analog Sensor
Nickel
Nickel, Platinum, A99B, 2.25k ohm NTC,
10k ohm NTC, 10k ohm NTC Type 3
0
-5 to 5 (°F or °C based on Units setting
under Display Settings menu)
0
-5 to 5 (°F or °C based on Units setting
under Display Settings menu)
Nickel
Nickel, Platinum, A99B, 2.25k ohm NTC,
10k ohm NTC, 10k ohm NTC Type 3
False
True or False
Automatic PID
Automatic PID Tuning, Manual PID
Tuning
Tuning, Deadband Override, On/Off
Control (Single-stage Models)
No
Yes or No