Johnson Controls TEC3010 Installation Instructions Manual page 41

Tec3000 series wireless single- or two-stage economizer thermostat controllers
Hide thumbs Also See for TEC3010:
Table of Contents

Advertisement

Table 12: Fault List (Part 3 of 4)
Faults
Humidity Unreliable
Controller Fault
Touchscreen Unavailable
Board Mismatch
Firmware Mismatch
USB Malfunction
Supply Fan Runtime Limit
Extended
Heating Ineffective
Cooling Ineffective
Supply Fan Fault
TEC3000 Series Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
Probable Causes
The zone humidity reading was reliable
and has now failed.
The controller has detected an internal
fault that it cannot recover.
An unknown error has prevented the
controller from turning on.
The touchscreen components have
failed to initialize.
The baseboard and CPU board are
paired incorrectly. An error message
appears on the TEC indicating the
model number of the baseboard and
CPU board.
The previous upgrade has not
completed.
The previous downgrade has not
completed because the previous
version is no longer supported.
A USB drive has malfunctioned and
drawn more than the maximum allowed
current.
The Supply Fan Runtime has exceeded
the configured Supply Fan Runtime
Limit.
The Supply Air Temperature has not
increased above the configured Supply
Air Temperature Alarm Offset while
heating has been active for at least the
Supply Air Temperature Alarm Delay.
The Supply Air Temperature has not
decreased below the configured Supply
Air Temperature Alarm Offset while
cooling has been active for at least the
Supply Air Temperature Alarm Delay.
The Supply Fan Status configured for
either BI1 or BI2 has not proved within
the configured Fan Alarm Delay.
Solutions
1. If the source of zone humidity was the
onboard sensor, contact Johnson Controls
product sales and support.
2. If the source of zone humidity was a BAS,
check the BAS to ensure that it is still online
and providing the TEC with the humidity
reading. If removal of the BAS mapping was
intentional, reset sensors through the menu.
Order replacement units and return the affected
devices to Johnson Controls under the RMA
program.
Order replacement units and return the affected
devices to Johnson Controls under the RMA
program.
1. Reboot the controller.
2. If problems persist, order replacement units
and return the affected devices to Johnson
Controls under the RMA program.
Match the baseboard to its corresponding CPU
board. See Table 2 for information on ensuring
that you have the CPU board and base board
paired correctly.
1. Upgrade the TEC3000 to the latest released
version.
2. Upgrade the TEC3000 to the current version
again.
Reboot the TEC3000 to clear the fault.
1. Attempt to insert and use the USB drive
again.
2. Try a new USB drive.
3. If problems persist, order replacement units
and return the affected devices to Johnson
Controls under the RMA program.
1. Service the Supply Fan.
2. Reset the Supply Fan runtime.
Verify that the heating elements on the rooftop
are functioning properly.
Verify that the cooling elements on the rooftop are
functioning properly.
1. Verify that the Supply Fan is operating when
turned on.
2. Verify that the Supply Fan Status wiring is
connected correctly.
41