Johnson Controls TEC3322-1 Series Installation Manual

Networked and wireless proportional fan coil and individual zone thermostat controllers with dehumidification capability
Hide thumbs Also See for TEC3322-1 Series:

Advertisement

Quick Links

TEC3000 Series Networked and Wireless Proportional Fan
Coil and Individual Zone Thermostat Controllers with
Dehumidification Capability
Installation Guide
TEC3322-1x-xxx, TEC3323-1x-xxx, TEC3622-1x-xxx, TEC3623-1x-xxx, TEC3022-1x-xxx, TEC3023-1x-xxx
Applications
The networked TEC3000 Series Thermostat Controllers are stand-alone and field-selectable BACnet® MS/TP or
N2 networked devices. Wireless networked models of the TEC3000 Series Thermostat Controller are also
available. Proportional Fan Coil and Individual Zone Thermostat Controllers provide control of the following:
Local hydronic reheat valves
Pressure-dependent variable air volume (VAV) equipment with or without local reheat
Two- or four-pipe fan coils
Cabinet unit heaters
Other individual zone equipment using an on/off or floating control input
The networked models feature a field-selectable Building Automation System (BAS) BACnet MS/TP or N2
communication capability that enables remote monitoring and programming for efficient space temperature control.
The wireless models are compatible with the WNC1800/ZFR182x Pro Series Wireless Field Bus System that
enables communication with a building automation system (BAS). All models include a USB port configuration that
reduces installation time by allowing simple backup and restore features from a USB drive, which enables rapid
cloning of configuration between like units.
Some models have occupancy sensing capability built into the device. These thermostat controllers maximize up to
30% energy savings in high-energy usage commercial buildings, such as schools and hotels, during occupied
times by using additional standby setpoints.
All models feature an intuitive onboard touchscreen UI with backlit display that makes setup and operation quick
and easy. For Single-or Two-Stage Economizer Thermostat Controller models, only the single-speed fan
configuration is supported. For TEC3x1x and TEC3x2x models, multiple fan configurations are supported for fan
coil equipment types, as follows:
Single-speed
Multi-speed (two or three discrete speeds)
Variable-speed/EC motors (0 to 10 VDC control)
Some models support dehumidification on two-pipe fan coil units with reheat, and four-pipe fan coil units with or
without reheat. When no heating is required, the thermostat controller monitors space humidity and activates
dehumidification control as necessary. Heat and/or reheat is used as required to maintain the space temperature.
For optimal dehumidification performance, use a fan coil unit that has a multi-speed or variable-speed fan (VSF).
TEC3000 Series Networked and Wireless Proportional Fan Coil and
Individual Zone Thermostat Controllers with Dehumidification Capability
Refer to the
QuickLIT website
Installation Guide
1
Issued May 2019
for the most up-to-date version of this document.
LIT-12013162

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls TEC3322-1 Series

  • Page 1 TEC3000 Series Networked and Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification Capability LIT-12013162 Issued May 2019 Installation Guide TEC3322-1x-xxx, TEC3323-1x-xxx, TEC3622-1x-xxx, TEC3623-1x-xxx, TEC3022-1x-xxx, TEC3023-1x-xxx Refer to the QuickLIT website for the most up-to-date version of this document. Applications The networked TEC3000 Series Thermostat Controllers are stand-alone and field-selectable BACnet®...
  • Page 2: North American Emissions Compliance

    IMPORTANT: The TEC3000 Series Thermostat Controller is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system.
  • Page 3 • Away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference • In a clear path between the integrated passive infrared (PIR) occupancy sensor (if equipped) and the space being monitored For wireless models, also locate the thermostat controller: •...
  • Page 4 Installing the thermostat controller 1. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls® T-4000-119 Allen-Head Adjustment Tool (order separately) to remove the security screw if it is installed on the top of the thermostat controller cover as illustrated in Figure 2.
  • Page 5 Figure 2: Removing the security screw from the thermostat controller cover (shown without occupancy sensor) (left) and removing the thermostat controller cover (right) 3. Align the thermostat controller mounting base on the wall with the security screw on the top and use the base as a template to mark the two mounting hole locations.
  • Page 6 Figure 3: Mounting hole locations, dimensions, in. (mm) (left) and securing the thermostat controller mounting base to the wall (right) Note: When the unit is mounted on the wall, you can hang the front cover on the end of the back cover as illustrated in Figure 4.
  • Page 7 Wiring When an existing thermostat controller is replaced, remove and label the wires to identify the terminal functions. Risk of Electric Shock. Disconnect the power supply before making electrical connections to avoid electric shock. Risque de décharge électrique. Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
  • Page 8 The bus EOL termination switch allows you to designate the thermostat controller as the end of the Field Controller (FC) Bus and N2 Bus. The default position is OFF. If the thermostat controller is at the end of a daisy chain of devices on the FC Bus and N2 Bus, set the EOL switch to the ON position.
  • Page 9 CPU board and the base board, the model is the TEC3612. 6. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000-119 Allen-Head Adjustment Tool (order separately) to reinstall the security screw on the top of the thermostat controller cover. See Figure 2 for security screw placement.
  • Page 10 Table 4: Terminal identification (See Figure 7 for wiring diagrams) Terminal label Function TEC3022, TEC3023, TEC3322, TEC3323, Proportional TEC3622, TEC3623 Proportional FC/VAV FC/VAV Proportional FC/VAV 24 V 24 VAC hot from transformer FAN H Fan high FAN M Fan medium FAN L Fan low and fan on Auxiliary binary output...
  • Page 11 Figure 7: Proportional wiring diagram (See Table 4 for terminal identification) TEC3000 Series Networked and Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification Capability Installation Guide...
  • Page 12 Figure 8: Proportional 0 to 10 VDC control (pressure-dependent VAV) Figure 9: Proportional 0 to 10 VDC control (pressure-dependent VAV with changeover sensor/switch) Figure 10: Proportional 0 to 10 VDC control (pressure-dependent VAV with changeover sensor/switch and reheat) TEC3000 Series Networked and Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification Capability Installation Guide...
  • Page 13 Figure 11: Floating control two-pipe heating and cooling hydronic valve control fan coil application Figure 12: Floating control two-pipe heating and cooling hydronic valve control with changeover fan coil application Figure 13: Proportional 0 to 10 VDC control (two-pipe and four-pipe fan coil applications) Cooling Valve Heating...
  • Page 14: Setup And Adjustments

    Figure 15: Binary input wiring Dry Contact Dry Contact Setup and adjustments IMPORTANT: Table 13 provides a full list of TEC3000 menu settings. In the upcoming sections, step-by-step instructions are included on how to access and adjust the more commonly used menus. Overview Figure 16 shows the thermostat controller home screen in both the light and dark themes.
  • Page 15: Customizing The Home Screen

    Figure 17: Thermostat controller home screen in cooling mode (left) and heating mode (right) Customizing the home screen Customizing the Home screen settings include: • Brightness • Units • Time Zone • Date • Enable Backlight • Time • Time Format •...
  • Page 16 Table 5: Touchscreen icons (Part 2 of 5) Icon Icon name Description Indicates the humidity reading. Humidity Standby Indicates that the unit is set to degrees. Degree Standby Network Communication Indicates that the thermostat controller detected a supervisory controller and both (for Networked Models) are online.
  • Page 17 Table 5: Touchscreen icons (Part 3 of 5) Icon Icon name Description Displays the current cooling setpoint. Indicates that Hold mode is disabled. To enable Hold mode, press the button. Cooling Setpoint Displays the current heating setpoint. Indicates that Hold mode is disabled. To enable Hold mode, press the button.
  • Page 18 Table 5: Touchscreen icons (Part 4 of 5) Icon Icon name Description Fan Overrides for Adjusts the fan override between Low, Medium, High, Auto, and Quiet for Multi-speed Fans multi-speed fans. Medium High Auto Quiet Occupancy Status Adjusts the occupancy between Unoccupied, Occupied, Temporarily Occupied, Standby, Occupancy Override, Unoccupancy Override.
  • Page 19: User Lockout

    Table 5: Touchscreen icons (Part 5 of 5) Icon Icon name Description Deletes the scheduled event. Delete Clears the password entry on the keypad screen. Clear Indicates that an error has occurred. Exclamation point User lockout You can select from three different levels of access at the local display to manage functionality through the supervisory controller.
  • Page 20 The TEC3000 firmware update is complete when the TEC3000 restarts and returns to the home screen. Backing up the settings Note: When you back up the settings, the network settings are not backed up or restored. 1. Ensure that the TEC screen is on. 2.
  • Page 21 9. Press BACnet Instance ID. 10. Enter the unique BACnet® instance ID using the keypad. This value should be different to the other controllers on the site. 11. Press Save. 12. Press the back arrow to return to the previous screen. 13.
  • Page 22 Configuring the thermostat controller Use the Menu icon on the home screen to access and change the basic operating parameters of the thermostat controller. During normal operation, press the Menu icon once to access the following parameters: • Fault Status •...
  • Page 23: Setting The Control Mode

    4. Press Supply Fan. 5. Press Supply Fan Type and select Single Speed, Multi-Speed, or Variable Speed. 6. Press Save and the back arrow to return to the previous screen. For multi-speed fan control, you can adjust the point when the medium or high speed turns on. The fan speed is based on the load of the cooling/heating device, and is a percentage between 0 and 100.
  • Page 24 Setting the Fan mode - fan coil only The Fan Mode informs the controller how to handle the fan. There are two options for fan configuration: a Fan Mode available to the installer through the menu system, and a fan override available as an option to the end user from the Fan icon on the home screen.
  • Page 25 To set the Equipment Size parameter: 1. Press the Menu icon. Press Control Setup. 3. Press Tuning. 4. Use the up and down arrows to navigate to Equipment Size. 5. Press Equipment Setup and select Oversized. 6. Press Save and the back arrow to return to the previous screen. Changeover Pressure-Dependent VAV systems and two-pipe fan coils require changeover detection in order to switch seasonal operation between heating and cooling modes.
  • Page 26: Temperature Setpoints

    Dehumidification control - fan coil only The TEC3000 controller support dehumidification control on fan coil devices under three configurations: • Four-pipe fan coil • Four-pipe fan coil with reheat • Two-pipe fan coil (with changeover in cooling mode) with reheat For optimal dehumidification performance, a 4-pipe unit with floating/incremental or 0 to 10 V control and a multi- speed or variable-speed fan is recommended.
  • Page 27 The occupant has access to an up/down adjustment from the home screen. This adjustment applies a fixed offset (+/-) to the currently active setpoint, and this offset holds until the occupancy state of the controller changes. If the user taps the setpoint on the home screen, the icon inverts and displays white text on a black icon. The offset is held throughout all occupancy periods.
  • Page 28 Occupancy is determined using a top-down decision matrix as shown in Table 8. Enumerations may not match the TEC3000 Series Networked and Wireless Proportional Fan Coil and Individual LIT-12013162 Zone Thermostat Controllers with Dehumidification Capability Installation Instructions ( ) and the TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Technical Bulletin (LIT- 12011956) for NAE releases prior to 7.x.
  • Page 29 If the OCC-CONFIG is set to Schedule, the internal schedule commands the LOCAL-OCC object, which sets the Occupancy Schedule command. Note: If you do not have a schedule in the Schedule object and you have the OCC-CONFIG set to Schedule, you can control the unit with the LOCAL-OCC object externally;...
  • Page 30 5. Select the days to which the schedule should apply. Note that if events are already set for the selected days, they appear in the corresponding event box. If any events conflict between selected days, an asterisk appears in the event box. See Figure 18. 6.
  • Page 31 9. Press Save to save the completed event or Trash to delete the completed event. See Figure 21. The screen resets to the Event 1 Set Schedule screen. Note: If you do not select Save at this point, the event is not saved and you must repeat the event selection sequence.
  • Page 32 PID is used in conjunction with a Multi-Stage Controller (MSC) for all occupied and standby control. Additionally, the PID features Johnson Controls proprietary PRAC+ (Pattern Recognition Adaptive Control) automatic tuning, which continuously tunes the controller parameters to automatically optimize the control performance to match the equipment and zone.
  • Page 33 2. Press Setup. 3. Press General Control Setup. 4. Press Tuning. 5. Press Temp Control Setup. 6. Select Manual PID Tuning (or any option listed in Table 10). 7. Press Save and the back arrow to return to the previous screen. As a result of disabling PRAC+ Automatic Tuning, you have access to different types of manual tuning that allows modifications of tuning parameters listed under Control Setup >...
  • Page 34: Aux Control

    The polarity of the inputs are provided in Table 11. Table 11: Input polarities BI configuration Contact open Contact closed Occupancy Unoccupied Occupied Temp Occ No Trigger Active Temporary Occupancy Trigger Motion NO No Motion Detected, Standby Motion Detected, Occupied Motion NC No Motion Detected, Standby Motion Detected, Occupied...
  • Page 35: Commissioning Mode

    Commissioning mode The thermostat controller has a built-in commissioning mode, which is designed to allow you to quickly test equipment wiring and functionality. Commissioning mode temporarily disables the control logic, and allows you to manually command any individual output. Commissioning is designed to be the last step of the installation process after configuring the controller for the equipment being controlled, and the available options in commissioning mode are dependent on the controller configuration.
  • Page 36 b. Press Menu > Setup > Input Setup > AI1 Offset and select the temperature offset as needed for the sensor connected to RSEN. The options are -5°F to 5°F or -2.8°C to 2.8°C. • If the selected sensor is a Relative Humidity, Carbon Dioxide, or Damper feedback sensor, the Input Setup is automatically set to 0-10 VDC.
  • Page 37: Menus And Submenus

    • Supply Fan Runtime—The TEC3000 supports setting runtime limits on the supply fan command. When the limit is exceeded, an alarm turns on. This feature is intended to be used as a maintenance reminder. Setting the runtime limit to 0 disables this feature. •...
  • Page 38 Table 13: Menus and submenus (Part 2 of 6) Level 1 Level 2 (LCD screen name) Display Settings Passcode Enabled Passcode* Brightness Setting Enable Backlight Timeout Units Time Time Zone Set Time Format Date Set Date Format Language Show Fan Button on Home Show Temp on Home Show Humidity on Home Show Off Button on Home...
  • Page 39 Table 13: Menus and submenus (Part 3 of 6) Level 1 Level 2 (LCD screen name) Setup General Control Setup Control Mode Unit Enable Fan Mode* Max Setpoint Offset Fan On Delay* Fan Off Delay* Frost Protection Dehum Enable* Aux Mode Load Shed Rate Limit Load Shed Adjust Fan Alarm Delay...
  • Page 40 Table 13: Menus and submenus (Part 4 of 6) Level 1 Level 2 (LCD screen name) Setup (Cont) Auto Economizer Tuning Heat Prop Band* Heat Integral Time* Heat Process Range* Heat Saturation Time* Heat Time Constant* Heat Process Dead Time* Heat Period* Cool Prop Band* Cool Integral Time*...
  • Page 41 Table 13: Menus and submenus (Part 5 of 6) Level 1 Level 2 (LCD screen name) Equipment Setup (Cont) Minimum Command* Medium Speed On Cmd* High Speed On Cmd* Reheat Reheat Installed Reheat Min Damper Pos* Reheat Fan Required* Changeover Changeover Mode* Supply Temp Type* Changeover Setpoint*...
  • Page 42 Table 13: Menus and submenus (Part 6 of 6) Level 1 Level 2 (LCD screen name) Commissioning Supply Air Temperature Heat Command Cool Command Supply Fan Update View Version Load Firmware Restore* Backup* Network Status (for wireless Radio Code Version models) Radio PAN ID Active Channel...
  • Page 43 Table 14: TE-6300 Series Temperature Sensors (order separately) (for wireless TEC models) (Part 2 of 2) Sensor type Mounting style Probe length Product code number Platinum Adjustable 8 in. (203 mm) TE-6351-A (1k ohm) Duct 4 in. (102 mm) TE-635GM-1 8 in.
  • Page 44: Troubleshooting

    Internal Sensor Fail An internal sensor has failed on the Order replacement units and return the affected TEC. devices to Johnson Controls under the RMA program. Dehum Unavailable Dehumidification is unavailable 1. If the source of zone humidity was a BAS,...
  • Page 45 Controller Fault The controller has detected an internal Order replacement units and return the affected fault that it cannot recover. devices to Johnson Controls under the RMA program. An unknown error has prevented the Order replacement units and return the affected controller from turning on.
  • Page 46 Table 15: Fault list (Part 3 of 3) Faults Probable causes Solutions Cooling Ineffective The Supply Air Temperature has not Verify that the cooling elements on the rooftop are decreased below the configured Supply functioning properly. Air Temperature Alarm Offset while cooling has been active for at least the Supply Air Temperature Alarm Delay.
  • Page 47 A hardware failure is causing the Order replacement units and return the affected two boards to incorrectly identify devices to Johnson Controls under the RMA themselves. program. The controller displays Controller An internal fault was detected Order replacement units and return the affected Fault.
  • Page 48: Repair Information

    Repair information If the TEC3000 Series Thermostat Controller fails to operate within its specifications, replace the unit. For a replacement thermostat controller, contact the nearest Johnson Controls representative. Technical specifications TEC3000 Series Networked and Wireless Proportional Fan Coil and Individual Zone Thermostat...
  • Page 49: Software Terms

    The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products.
  • Page 50 Building Technologies & Solutions 507 E. Michigan Street, Milwaukee, WI 53202 Metasys® and Johnson Controls® are registered trademarks of Johnson Controls. All other marks herein are the marks of their respective owners. © 2019 Johnson Controls. Installation Guide Published in U.S.A.

Table of Contents