Johnson Controls TEC3010 Installation Instructions Manual page 8

Tec3000 series wireless single- or two-stage economizer thermostat controllers
Hide thumbs Also See for TEC3010:
Table of Contents

Advertisement

Table 3: Terminal Identification (See Figure 6 for Wiring Diagram)
Terminal Label
Function
TEC3030, TEC3031
24 V
24 VAC hot from the sensor
Y1
Cooling stage 1
Y2
Cooling stage 2
OAD
Economizer
AUX
Auxiliary output
AUX
Auxiliary output
W1 OB
Heating 1 (RTU mode)/Reversing valve (O/B) (Heat Pump mode)
1
Power for W1 and W2
RH
W2 SUP
Heating 2 (RTU mode)/Supplemental heat (Heat Pump mode)
OAT
Outside air temperature
Common
2
COM
G
Fan
BI2
Configurable binary input 2
BI1
Configurable binary input 1
SAT
Supply temperature sensor
R SEN
Zone temperature sensor
1.
RH needs to be connected for W1 and W2 to energize. For heating systems with an isolated power
supply, connect RH to the R terminal of the heating system. For systems that switch the hot supply
to the heating commands, connect the jumper to 24 V. For systems that switch the neutral supply to
the heating commands, connect the jumper to COM.
2.
The common terminals are connected and can be used for all inputs, outputs, and 24 VAC power.
TEC3000 Series Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions