Commissioning Mode; Sensor Priority; Available Fault Diagnostics - Johnson Controls TEC3010 Installation Instructions Manual

Tec3000 series wireless single- or two-stage economizer thermostat controllers
Hide thumbs Also See for TEC3010:
Table of Contents

Advertisement

Off—Output is turned off (relay open), used by a BAS to directly control the AUX output
To set the Aux Mode:
1. Press the Menu icon.
2. Press Control Setup.
3. Press General.
4. Press Aux Mode and set accordingly.
5. Press
to save and
This option is also exposed to the BAS through the point AUX-MODE.

Commissioning Mode

The thermostat controller has a built-in commissioning mode, which is designed to allow you to quickly test
equipment wiring and functionality. Commissioning mode temporarily disables the control logic, and allows you to
manually command any individual output. Commissioning is designed to be the last step of the installation process
after configuring the controller for the equipment being controlled. The available options in commissioning mode
are dependent on the controller configuration. To enter commissioning mode:
1. Press the Menu icon.
2. Select Commissioning.
3. Confirm that the selection was intentional. (The control is overridden upon selecting Confirm).
Individual outputs can be commanded through this interface. For binary outputs, the options are Off or On; for
analog outputs, they can be commanded from 0 to 100%. Whenever a control output is turned on, the fan is
engaged for safety purposes. To command an output from the Commissioning menu:
1. Select the output to command. Adjust the value to the preferred output and press Save. The output
immediately changes to that value.
2. Restore the value to the original setting and press Save once again to complete testing that output.
Pressing the back icon from the main commissioning menu or allowing the menu system to time out and return to
the home screen ends commissioning and puts the control logic back in control of the outputs.

Sensor Priority

The TEC3000 supports various sources of sensor data for use in control or display, including internal sensors,
remote sensors (connected using an analog input), or network commanded sensors. The TEC uses the highest
priority connected input (network commands followed by remote sensors and then internal sensors) for control and
display. Not all sources are available for all sensors.
Network commands operate on a timeout basis. When a network point is written to by a supervisor, the point
becomes the highest priority for 15 minutes. If a new update is written within 15 minutes, the timer is restarted for
another 15 minutes.

Available Fault Diagnostics

Supply Fan Faults—The TEC3000 supports a configurable Supply Fan Status feedback input that turns on
when the Supply Fan Status does not match the Supply Fan Command, and can be configured to disable
heating, cooling, and fan commands. The alarm delay is adjustable through the Fan Alarm delay setting. If the
delay is set to 0 or the binary input is not defined, this feature becomes disabled.
Supply Fan Runtime—The TEC3000 supports setting runtime limits on the supply fan command. When the
limit is exceeded, an alarm turns on. This feature is intended to be used as a maintenance reminder. Setting
the runtime limit to 0 disables this feature.
TEC3000 Series Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
to return to the previous screen.
27

Advertisement

Table of Contents
loading

Table of Contents