Overriding The Occupancy Mode; Enabling Optimal Start; Pid/Prac+ Automatic Control Tuning - Johnson Controls TEC3010 Installation Instructions Manual

Tec3000 series wireless single- or two-stage economizer thermostat controllers
Hide thumbs Also See for TEC3010:
Table of Contents

Advertisement

Overriding the Occupancy Mode

The TEC supports a manual override of all other schedule sources (for example, Schedule, Occupancy BI, and
temporary occupancy). This override can be set as follows:
1. Press the Menu icon.
2. Press Schedule.
3. Press Schedule Options.
4. Press Manual Occupancy Mode and select Occupied, Unoccupied, or No Override.
5. Press
to save and
This option is also exposed to the BAS through the point OCCOVRD-MODE.

Enabling Optimal Start

The TEC supports an advanced optimal start algorithm. The algorithm works in conjunction with a local schedule to
pre-heat or pre-cool the zone before scheduled occupancy periods begin, in order to bring the zone to the desired
occupied setpoint when the scheduled occupancy period begins. Occupant comfort is ensured while automatically
minimizing energy usage. This algorithm creates a model of the zone being controlled and automatically
determines when to start the equipment before the scheduled transition to Occupied. The start time automatically
adjusts daily in order to minimize the time between reaching setpoint and entering Occupied state.
Note: Optimal Start does not work when the schedule source is set to External.
To enable this feature:
1. Press the Menu icon.
2. Press Schedule.
3. Press Schedule Options.
4. Press Optimal Start Enable and select Yes.
5. Press
to save and
Enabling the Motion Sensor (TEC3x31-00-000 Models)
By default on models with integral motion sensing capability, the motion sensor is enabled with a default timeout of
15 minutes from the last detection of motion in the zone. On models without an integrated sensor, the default
timeout is still 15 minutes, but it only is applied when one of the two configurable binary inputs is set to be a motion
sensor (see Configurable Binary Inputs for information on configuring the binary inputs). To disable motion sensing
capabilities, set the Motion Sensor Timeout to 0 minutes. See Table 7 to view the available setpoints. See Table 9
to view the setpoint values. To adjust the motion sensor timeout:
1. Press the Menu icon.
2. Press Schedule.
3. Press Schedule Options.
4. Press Motion Sensor Timeout and adjust accordingly.
5. Press
to save and

PID/PRAC+ Automatic Control Tuning

The TEC3000 features advanced proportional-integral-derivative (PID) control algorithms to maximize control
performance while minimizing excessive cycling and wear on the equipment. PID and PRAC+ (Pattern Recognition
Adaptive Control) are used in conjunction with a Multi-Stage Controller (MSC) for all occupied and standby control.
TEC3000 Series Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
to return to the previous screen.
to return to the previous screen.
to return to the previous screen.