Johnson Controls TEC3010 Installation Instructions Manual page 32

Tec3000 series wireless single- or two-stage economizer thermostat controllers
Hide thumbs Also See for TEC3010:
Table of Contents

Advertisement

Table 10: Menus and Submenus (Part 4 of 9)
Level 1
Level 2
(LCD Screen Name)
Control Setup
Deadband*
(Cont)
Auto Economizer Tuning
Heat Prop Band*
Heat Integral Time*
Heat Process Range*
Heat Saturation Time*
Heat Time Constant*
Heat Process Dead Time*
Heat Period*
Cool Prop Band*
Cool Integral Time*
Cool Process Range*
Cool Saturation Time*
Cool Time Constant*
Cool Process Dead Time*
Cool Period*
TEC3000 Series Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
Level 3
Available Values
(Default Values)
0.7 to 1.5°F
1.0°F (-17.22 °C)
*Functionally, this is the PID deadband
when the Temp Control Setup is equal to
the Deadband Override or Manual PID
Tuning. When the Temp Control Setup
equals the On/Off Control, the
Deadband is used for the On/Off range
of the stage equipment. This parameter
is hidden when Temp Control Setup
equals Automatic PID Tuning.
Enable
Disable or Enable
160°F
5 to 10°F (-15 to -1.11°C)
*Values only appear when the Temp
control equals Manual PID Tuning.
729 seconds
300 to 1,600 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
40°F
10 to 100°F (-12.22 to 37.77°C)
*Values only appear when the Temp
control equals Manual PID Tuning.
600 seconds
60 to 900 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
720 seconds
360 to 1,440 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
72 seconds
20 to 120 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
60 seconds
30 to 120 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
160°F
5 to 10°F (-15 to -1.11°C)
*Values only appear when the Temp
control equals Manual PID Tuning.
729 seconds
300 to 1,600 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
40°F
10 to 100°F (-12.22 to 37.77°C)
*Values only appear when the Temp
control equals Manual PID Tuning.
600 seconds
60 to 900 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
720 seconds
360 to 1,440 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
72 seconds
20 to 120 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.
60 seconds
30 to 120 seconds
*Values only appear when the Temp
control equals Manual PID Tuning.