Johnson Controls TEC3010 Installation Instructions Manual page 33

Tec3000 series wireless single- or two-stage economizer thermostat controllers
Hide thumbs Also See for TEC3010:
Table of Contents

Advertisement

Table 10: Menus and Submenus (Part 5 of 9)
Level 1
Level 2
(LCD Screen Name)
Control Setup
Econ Prop Band*
(Cont)
Econ Integral Time*
Econ Process Range*
Econ Saturation Time*
Econ Time Constant*
Econ Process Dead Time*
Econ Period*
Equipment Size
Network Setup
FC Comm Mode
BACnet Instance ID*
BACnet Device Address*
BACnet Encoding Type
BACnet/MSTP Communication Mode
Pan ID
TEC3000 Series Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
Level 3
Available Values
(Default Values)
160°F
5 to 10°F (-15 to -1.11°C)
*Values only appear when Auto
Economizer Tuning is Disabled.
729 seconds
300 to 1,600 seconds
*Values only appear when Auto
Economizer Tuning is Disabled.
40°F
10 to 100°F (-12.22 to 37.77°C)
*Values only appear when Auto
Economizer Tuning is Disabled.
600 seconds
60 to 900 seconds
*Values only appear when Auto
Economizer Tuning is Disabled.
720 seconds
360 to 1,440 seconds
*Values only appear when Auto
Economizer Tuning is Disabled.
72 seconds
20 to 120 seconds
*Values only appear when Auto
Economizer Tuning is Disabled.
60 seconds
30 to 120 seconds
*Values only appear when Auto
Economizer Tuning is Disabled.
Normal
Normal or Oversized
*Value only appears when Temp Control
Setup is not equal to On Off Control
Wireless Field Bus
1
0 to 4,914,302
* BACnet/MSTP communication mode
4
4 to 127
* BACnet/MSTP communication mode
ISO 10646
ISO 10646 (UCS-2), ANSI X3.4
(UCS-2)
(US-ASCII)
65535
0 to 127
33
1