Johnson Controls TEC3010 Installation Instructions Manual page 15

Tec3000 series wireless single- or two-stage economizer thermostat controllers
Hide thumbs Also See for TEC3010:
Table of Contents

Advertisement

3. Press the Menu icon.
4. Scroll down the menu and press Update.
5. Press Load Firmware.
6. Select the correct firmware version. The correct file name has the .pkg extension.
7. Press Confirm if you have the correct firmware version.
The firmware is loaded from the USB drive. See Troubleshooting if the firmware is not loaded correctly.
8. Remove the USB drive from the TEC3000.
Backing Up the Settings
Note: When you back up the settings, the network settings are not backed up or restored.
1. Ensure that the TEC screen is on.
2. Insert the USB drive into the right side of the TEC.
See Figure 1 for the USB port location.
3. Press the Menu icon.
4. Scroll down the menu and press Update.
5. Press Backup.
A message appears, stating that the file is saved locally and on a USB drive.
6. Press Confirm to save locally and on USB.
The setting files are named based on the TEC3000 model name, date, and time stamp
(for example, TEC3031-00_2015-10-08T1), They are saved locally and on the USB drive's root directory. See
Troubleshooting if the settings are not backed up correctly.
7. After the settings are saved onto the USB drive, remove the USB drive from the TEC3000.
Restoring the Settings
If the TEC3000 is connected to a network (for example, MSTP or wireless), you must manually set or verify, or
both, the BACnet Instance ID and BACnet Address in the Network Setup page after the Restore so they do not
conflict with other devices on the same network.
1. Ensure that the TEC screen is on.
2. Insert the USB drive into the right side of the TEC.
See Figure 1 for the USB port location.
3. Press the Menu icon.
4. Press Update.
5. Press Restore.
6. Select Local Storage or the correct configuration file that was created from a previous backup operation.
The setting files are named based on the TEC3000 model name, date, and time stamp
(for example, TEC3031-00_2015-10-08T1), They are saved locally and on the USB drive's root directory.
7. Press Confirm if you have the correct file name.
The settings are loaded from the USB drive.
8. After the settings are loaded from the USB drive, remove the USB drive from the TEC3000.
Configuring the Network Settings
1. Ensure the TEC screen is on.
2. Press the Menu icon.
TEC3000 Series Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
15

Advertisement

Table of Contents
loading

Table of Contents