Device (Dv) Object - Mitsubishi Electric MELSEC iQ-F Series User Manual

Programmable controller
Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

Device (DV) object

This object indicates the Ethernet module.
Property list
The following table lists available properties for the Device object.
Additionally, the availability of reading/writing data from/to a BACnet device is shown in the following table.
R: Read-only, W: Read/Write
PropertyID
Property
11
ApduTimeout
12
ApplicationSoftwareVersion
30
DeviceAddressBinding
44
FirmwareRevision
56
LocalDate
57
LocalTime
62
MaxApduLengthAccepted
70
ModelName
73
NumberOfAPDURetries
75
ObjectIdentifier
76
ObjectList
77
ObjectName
79
ObjectType
96
ProtocolObjectTypesSupported
97
ProtocolServicesSupported
98
ProtocolVersion
107
SegmentationSupported
112
SystemStatus
120
VendorIdentifier
121
VendorName
139
ProtocolRevision
4 FUNCTIONS
44
4.2 BACnet Object Function
Data type
Unsigned
CharacterString
ListofBACnetAddressBinding
CharacterString
Date
Time
Unsigned
CharacterString
Unsigned
BACnetObjectIdentifier
BACnetARRAY[N]ofBACnetObjectIdentifi
er
CharacterString
Enumerated
BitString
BitString
Unsigned
Enumerated
Enumerated
Unsigned16
CharacterString
Unsigned
R/W
Description
R
Indicates the resending time interval.
The Ethernet module is 0 (Retry, Timeout)
R
Indicates the application software version.
The Ethernet module is 0.
R
Indicates the list of device IDs and
addresses of other devices.
R
Indicates a character string indicating the
version.
In the case of Ver.1.100, it will be 1100.
R
Indicates the date of the device.
R
Indicates the time of the device.
R
Indicates the maximum length of the
APDU to be accepted.
The Ethernet module is 1024.
R
Indicates the character string for a 12-
character and left-justified model name.
The Ethernet module is FX5-ENET.
R
Indicates the maximum number of
resends.
The Ethernet module is 0 (Retry, Timeout)
R
Indicates the ID to identify the object.
R
Indicates the list of objects in the device.
R
Indicates the object name.
R
Indicates the object type.
R
Indicates the objects supported.
R
Indicates the services supported.
R
Indicates the version of the BACnet
protocol supported.
The Ethernet module is 1.
R
Indicates whether or not message
segmentation is supported.
The Ethernet module does not support it.
R
Indicates the device status.
R
Indicates the vendor identifier code
assigned by ASHRAE.
The Ethernet module is 434.
R
Indicates the manufacturer of the device.
The Ethernet module is Mitsubishi Electric
Corporation Nagoya Works.
R
Indicates the revision level to be
supported.
The level varies depending on the
standard set with the engineering tool.
The standards for the Ethernet module are
as follows.
• ANSI/ASHRAE Standard 135-2016: 20
• ANSI/ASHRAE Standard 135-2012: 14
• ANSI/ASHRAE Standard 135-2010: 12
• ANSI/ASHRAE Standard 135-2004: 4
• IEIEJ-G-0006:2006 Addendum-a

Advertisement

Table of Contents
loading