AnalogOutput (AO) object

This object handles analog output.
Property list
The following table lists available properties for the AnalogOutput object.
Additionally, the availability of reading/writing data from/to a BACnet device is shown in the following table.
R: Read-only, W: Read/Write
PropertyID
Property
36
EventState
75
ObjectIdentifier
77
ObjectName
79
ObjectType
81
OutOfService
85
PresentValue
87
PriorityArray
103
Reliability
104
RelinquishDefault
111
StatusFlags
117
Units
*1
371
PropertyList
431
CurrentCommandPriority
*1 Only ANSI/ASHRAE Standard 135-2016 and ANSI/ASHRAE Standard 135-2012 are supported.
*2 Only ANSI/ASHRAE Standard 135-2016 is supported.
Buffer memory format of the AnalogOutput object
For the format of the properties assigned to the buffer memory, refer to the following.
Page 86 BACnet communication AnalogOutput
Ethernet module operation
■Operation at startup
For the startup operation, refer to the following.
Page 22 Ethernet module operation
■Operation of PresentValue for the output/value object
For the operation of PresentValue for the output/value object, refer to the following.
Page 23 PresentValue for the output/value object
Setting using a program
For the setting using the program, refer to the following.
Page 26 Setting using a program
Data type
Enumerated
BACnetObjectIdentifier
CharacterString
Enumerated
BOOLEAN
REAL
BACnetPriorityArray
Enumerated
REAL
BitString
Enumerated
BACnetARRAY[N]ofBACnetPropertyIdenti
fier
*2
BACnetOptionalUnsigned
R/W
Description
R
Indicates the event status.
R
Indicates the ID to identify the object.
R
Indicates the object name.
R
Indicates the object type.
W
Indicates whether the device is
disconnected from the physical output.
W
Indicates the current value of the output.
R
Indicates an array of priority values for
determining the output value.
R
Indicates reliability.
W
Indicates the default value to be used
when all values of PriorityArray are NULL.
R
Indicates the object status.
R
Indicates the unit.
R
Indicates the property list.
R
Indicates the PriorityArray array number
used for PresentValue.
4 FUNCTIONS
4.2 BACnet Object Function
4
35