Mitsubishi Electric MELSEC iQ-F Series User Manual page 90

Programmable controller
Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

BACnet communication AnalogValue
■BACnet communication AnalogValue (Un\G8920 to Un\G9071)
This buffer memory area is used for the AnalogValue object.
Address
Un\G8920 to Un\G8931
Un\G8940 to Un\G8951
Un\G8960 to Un\G8971
Un\G8980 to Un\G8991
Un\G9000 to Un\G9011
Un\G9020 to Un\G9031
Un\G9040 to Un\G9051
Un\G9060 to Un\G9071
When the value of `Module READY` (Un\G34, b0) was changed from 0 to 1, the AnalogValue object settings
are reflected. ( Page 57 AnalogValue object setting)
The following table lists the buffer memory area format (BACnet communication AnalogValue 1) of the AnalogValue object.
Address
Name
Un\G8920,
Object ID
Un\G8921
Un\G8922,
PresentValue
Un\G8923
Un\G8924
OutOfService
Un\G8925
Reliability
Un\G8926,
Value setting value
Un\G8927
Un\G8928
Write setting
Un\G8929
Write control
Un\G8930
Update counter
APPX
88
Appendix 1 Buffer Memory
Description
BACnet communication AnalogValue 1
BACnet communication AnalogValue 2
BACnet communication AnalogValue 3
BACnet communication AnalogValue 4
BACnet communication AnalogValue 5
BACnet communication AnalogValue 6
BACnet communication AnalogValue 7
BACnet communication AnalogValue 8
Description
b0 to b9: Object type
Stores the object type. (Fixed at 2)
b10 to b31: Instance
Stores the instance number. (0 to 4194303)
number
Stores the current analog value. (Within the 32-bit floating-point data type real
number)
b0: OutOfService
Sets the value of the OutOfService property.
• ON: TRUE
• OFF: FALSE
b0 to b5: Reliability
Stores the value of the Reliability property.
• 0: NoFaultDetected
• 1: NoSensor
• 2: OverRange
• 3: UnderRange
• 4: OpenLoop
• 5: ShortedLoop
• 6: NoOutput
• 7: UnreliableOther
• 8: ProcessError
• 9: MultiStateFault
• 10: ConfigurationError
Sets the analog value to be written to PriorityArray. (Within the 32-bit floating-
point data type real number)
b0: Null setting flag
Sets whether or not to write Null to PriorityArray.
• ON: Write
• OFF: Do not write
b1 to 5: Priority
Sets the priority for writing to PriorityArray. (1 to 16)
b0: Write flag
Sets whether or not to write the Value setting value to PriorityArray.
The write flag is enabled when OutOfService is set to OFF (FALSE).
• ON: Write
• OFF: Do not write
Stores the number of times PresentValue was updated. (0 to 32767)
*1
*2

Advertisement

Table of Contents
loading

Table of Contents