■AnalogValue object setting
Item
Instance No.
Object Name
Units (Select)
Units (Input)
Relinquish_Default
■BinaryInput object setting
Item
Instance No.
Object Name
Polarity
Inactive_Text
Description
Set an instance number for the AnalogValue object. (The same
value cannot be set in the AnalogValue object.)
Set an object name for the AnalogValue object. (The same value
cannot be set in a module.)
Set a unit. (The value can be set only when "Other" is selected in
the drop-down menu.)
Input a setting value when Units (Select) is set to "Other".
Set the value that will be set when PriorityArray is all NULL.
Description
Set an instance number for the BinaryInput object. (The same value
cannot be set in the BinaryInput object.)
Set an object name for the BinaryInput object. (The same value
cannot be set in a module.)
Set a polarity.
Set the text to be displayed at Inactive.
Setting range
0 to 4194303
(Default: Empty)
16 one-byte alphanumeric
characters maximum
(Default: Empty)
• 0: square-meters
• 1: square-feet
• 2: milliamperes
• 3: amperes
• 4: ohms
• 5: volts
• 6: kilovolts
• 7: megavolts
• 8: volt-amperes
• 9: kilovolt-amperes
• Others
(Default: 0: square-meters)
10 to 65535
(Default: Empty)
32-bit floating point
-38
38
1.1810
to 3.410
(Default: 0)
Setting range
0 to 4194303
(Default: Empty)
16 one-byte alphanumeric
characters maximum
(Default: Empty)
• Positive polarity
• Negative polarity
(Default: Positive polarity)
16 one-byte alphanumeric
characters maximum
(Default: Empty)
6 PARAMETER SETTINGS
6.3 Basic Settings
6
57