Analogvalue (Av) Object - Mitsubishi Electric MELSEC iQ-F Series User Manual

Programmable controller
Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

AnalogValue (AV) object

This object handles values such as analog setting values.
Property list
The following table lists available properties for the AnalogValue object.
Additionally, the availability of reading/writing data from/to a BACnet device is shown in the following table.
R: Read-only, W: Read/Write
PropertyID
Property
36
EventState
75
ObjectIdentifier
77
ObjectName
79
ObjectType
81
OutOfService
85
PresentValue
87
PriorityArray
103
Reliability
104
RelinquishDefault
111
StatusFlags
117
Units
371
PropertyList
431
CurrentCommandPriority
*1 Only ANSI/ASHRAE Standard 135-2016 and ANSI/ASHRAE Standard 135-2012 are supported.
*2 Only ANSI/ASHRAE Standard 135-2016 is supported.
Buffer memory format of the AnalogValue object
For the format of the properties assigned to the buffer memory, refer to the following.
Page 88 BACnet communication AnalogValue
4 FUNCTIONS
36
4.2 BACnet Object Function
*1
*2
Data type
Enumerated
BACnetObjectIdentifier
CharacterString
Enumerated
BOOLEAN
REAL
BACnetPriorityArray
Enumerated
REAL
BitString
Enumerated
BACnetARRAY[N]ofBACnetPropertyIdenti
fier
BACnetOptionalUnsigned
R/W
Description
R
Indicates the event status.
R
Indicates the ID to identify the object.
R
Indicates the object name.
R
Indicates the object type.
W
Indicates whether to change inside the
device.
W
Indicates the current analog value.
R
Indicates an array of priority values for
determining the output value.
R
Indicates reliability.
W
Indicates the default value to be used
when all values of PriorityArray are NULL.
R
Indicates the object status.
R
Indicates the unit.
R
Indicates the property list.
R
Indicates the PriorityArray array number
used for PresentValue.