BinaryInput (BI) object

This object handles binary input.
Property list
The following table lists available properties for the BinaryInput object.
Additionally, the availability of reading/writing data from/to a BACnet device is shown in the following table.
R: Read-only, W: Read/Write
PropertyID
Property
4
ActiveText
15
ChangeOfStateCount
16
ChangeOfStateTime
33
ElapsedActiveTime
36
EventState
46
InactiveText
75
ObjectIdentifier
77
ObjectName
79
ObjectType
81
OutOfService
84
Polarity
85
PresentValue
103
Reliability
111
StatusFlags
114
TimeOfActiveTimeReset
115
TimeOfStateCountReset
*1
371
PropertyList
*1 Only ANSI/ASHRAE Standard 135-2016 and ANSI/ASHRAE Standard 135-2012 are supported.
Buffer memory format of the BinaryInput object
For the format of the properties assigned to the buffer memory, refer to the following.
Page 90 BACnet communication BinaryInput
Ethernet module operation
■Operation at startup
For the startup operation, refer to the following.
Page 22 Ethernet module operation
Setting using a program
For the setting using the program, refer to the following.
Page 26 Setting using a program
Data type
CharacterString
Unsigned
BACnetDateTime
Unsigned32
Enumerated
CharacterString
BACnetObjectIdentifier
CharacterString
Enumerated
BOOLEAN
Enumerated
REAL
Enumerated
BitString
BACnetDateTime
BACnetDateTime
BACnetARRAY[N]ofBACnetPropertyIdenti
fier
R/W
Description
R
Indicates the text when the value of
PresentValue is ACTIVE.
W
Indicates the number of status changes
that have occurred.
R
Indicates the date and time when a status
change has occurred.
W
Indicates the integrated time when the
value of PresentValue is ACTIVE.
R
Indicates the event status.
R
Indicates the text when the value of
PresentValue is INACTIVE.
R
Indicates the ID to identify the object.
R
Indicates the object name.
R
Indicates the object type.
W
Indicates whether the device is
disconnected from the physical input.
W
Indicates polarity.
W
Indicates the logical state of the binary
input.
R
Indicates reliability.
R
Indicates the object status.
W
Indicates the date and time when
ElapsedActiveTime is set to 0.
W
Indicates the date and time when
ChangeOfStateCount is set to 0.
R
Indicates the property list.