Program that outputs information stored at a BACnet workstation
or BACnet controllers
The following describes an example of a program that outputs information stored at a BACnet workstation or BACnet
controllers.
Classification
Label name
Module label
M+FX5-ENET.bSts_ModuleReady_D
M+FX5-ENET.uBac_DV_SystemStatus_D
M+FX5-
ENET.unBac_DV_TimeSynchronization_D[1]
M+FX5-
ENET.bBac_DV_TimeSynchronization_Receive
d_Flag_D
M+FX5-ENET.eBAC_AO1_PresentValue_D
M+FX5-ENET.eBAC_AO1_SettingValue_D
M+FX5-ENET.uBAC_AO1_SettingWrite_D
M+FX5-ENET.uBAC_AO1_SettingControl_D
M+FX5-ENET.uBAC_AO1_Units_D
M+FX5-ENET.eBAC_AV1_PresentValue_D
M+FX5-ENET.bBAC_BO1_PresentValue_D
M+FX5-ENET.bBAC_BO1_FeedbackValue_D
M+FX5-ENET.udBAC_MO1_PresentValue_D
M+FX5-ENET.udBAC_MO1_FeedbackValue_D
Label to be defined
Define global labels as shown below.
Description
Module READY
SystemStatus
Time synchronization (year)
Time synchronization received flag
AnalogOutput1 PresentValue
AnalogOutput1: Value setting value
AnalogOutput1 PriorityArray
AnalogOutput1: Write control
AnalogOutput1 Units
AnalogValue1 PresentValue
BinaryOutput PresentValue
BinaryOutput1 FeedbackValue
Multi-stateOutput1 PresentValue
Multi-stateOutput1 FeedbackValue
Device
Un\G34.0
Un\G8500
Un\G8502
Un\G8509.0
Un\G8762
Un\G8766
Un\G8768
Un\G8769
Un\G8771
Un\G8922
Un\G9402.0
Un\G9409.0
Un\G10202
Un\G10212
7 PROGRAMMING
71
7.3 Program Examples