BinaryOutput (BO) object

This object handles binary output.
Property list
The following table lists available properties for the BinaryOutput object.
Additionally, the availability of reading/writing data from/to a BACnet device is shown in the following table.
R: Read-only, W: Read/Write
PropertyID
Property
4
ActiveText
15
ChangeOfStateCount
16
ChangeOfStateTime
33
ElapsedActiveTime
36
EventState
40
FeedbackValue
46
InactiveText
66
MinimumOffTime
67
MinimumOnTime
75
ObjectIdentifier
77
ObjectName
79
ObjectType
81
OutOfService
84
Polarity
85
PresentValue
87
PriorityArray
103
Reliability
104
RelinquishDefault
111
StatusFlags
114
TimeOfActiveTimeReset
115
TimeOfStateCountReset
371
PropertyList
431
CurrentCommandPriority
*1 Only ANSI/ASHRAE Standard 135-2016 and ANSI/ASHRAE Standard 135-2012 are supported.
*2 Only ANSI/ASHRAE Standard 135-2016 is supported.
Buffer memory format of the BinaryOutput object
For the format of the properties assigned to the buffer memory, refer to the following.
Page 91 BACnet communication BinaryOutput
4 FUNCTIONS
38
4.2 BACnet Object Function
*1
*2
Data type
CharacterString
Unsigned
BACnetDateTime
Unsigned32
Enumerated
Enumerated
CharacterString
Unsigned32
Unsigned32
BACnetObjectIdentifier
CharacterString
Enumerated
BOOLEAN
Enumerated
REAL
BACnetPriorityArray
Enumerated
REAL
BitString
BACnetDateTime
BACnetDateTime
BACnetARRAY[N]ofBACnetPropertyIdenti
fier
BACnetOptionalUnsigned
R/W
Description
R
Indicates the text when the value of
PresentValue is ACTIVE.
W
Indicates the number of status changes
that have occurred.
R
Indicates the date and time when a status
change has occurred.
W
Indicates the integrated time when the
value of PresentValue is ACTIVE.
R
Indicates the event status.
R
Indicates the feedback value.
R
Indicates the text when the value of
PresentValue is INACTIVE.
W
Indicates the minimum time that
PresentValue remains INACTIVE.
W
Indicates the minimum time that
PresentValue remains ACTIVE.
R
Indicates the ID to identify the object.
R
Indicates the object name.
R
Indicates the object type.
W
Indicates whether the device is
disconnected from the physical output.
W
Indicates polarity.
W
Indicates the logical state of the binary
input.
R
Indicates an array of priority values for
determining the output value.
R
Indicates reliability.
W
Indicates the default value to be used
when all values of PriorityArray are NULL.
R
Indicates the object status.
W
Indicates the date and time when
ElapsedActiveTime is set to 0.
W
Indicates the date and time when
ChangeOfStateCount is set to 0.
R
Indicates the property list.
R
Indicates the PriorityArray array number
used for PresentValue.