BACnet communication Multi-state Output
■BACnet communication Multi-state Output (Un\G10200 to Un\G10355)
This buffer memory area is used for the Multi-State Output object.
Address
Un\G10200 to Un\G10210, Un\G10212 to Un\G10215
Un\G10220 to Un\G10230, Un\G10232 to Un\G10235
Un\G10240 to Un\G10250, Un\G10252 to Un\G10255
Un\G10260 to Un\G10270, Un\G10272 to Un\G10275
Un\G10280 to Un\G10290, Un\G10292 to Un\G10295
Un\G10300 to Un\G10310, Un\G10312 to Un\G10315
Un\G10320 to Un\G10330, Un\G10332 to Un\G10335
Un\G10340 to Un\G10350, Un\G10352 to Un\G10355
When the value of `Module READY` (Un\G34, b0) was changed from 0 to 1, the Multi-State Output object
settings are reflected. ( Page 60 Multi-state Output object setting)
The following table lists the buffer memory area format (BACnet communication Multi-state Output 1) of the Multi-State Output
object.
Address
Name
Un\G10200,
Object ID
Un\G10201
Un\G10202,
PresentValue
Un\G10203
Un\G10204
OutOfService
Un\G10205
Reliability
Un\G10206,
Value setting value
Un\G10207
Un\G10208
Write setting
Un\G10209
Write control
Un\G10210
Update counter
Un\G10212,
FeedbackValue
Un\G10213
Un\G10214,
NumberOfStates
Un\G10215
*1 Stores the setting value of Multi-State Output object setting No.1.
*2 Null is written when the Null setting flag is on.
APPX
96
Appendix 1 Buffer Memory
Description
BACnet communication Multi-state Output 1
BACnet communication Multi-state Output 2
BACnet communication Multi-state Output 3
BACnet communication Multi-state Output 4
BACnet communication Multi-state Output 5
BACnet communication Multi-state Output 6
BACnet communication Multi-state Output 7
BACnet communication Multi-state Output 8
Description
b0 to b9: Object type
Stores the object type. (Fixed at 14)
b10 to b31: Instance
Stores the instance number. (0 to 4194303)
number
Stores the current 16-bit data value. (0 to NumberOfStates)
b0: OutOfService
Sets the value of the OutOfService property.
• ON: TRUE
• OFF: FALSE
b0 to b5: Reliability
Stores the value of the Reliability property.
• 0: NoFaultDetected
• 1: NoSensor
• 2: OverRange
• 3: UnderRange
• 4: OpenLoop
• 5: ShortedLoop
• 6: NoOutput
• 7: UnreliableOther
• 8: ProcessError
• 9: MultiStateFault
• 10: ConfigurationError
b0: PresentValue
Sets the 16-bit data to be written to PriorityArray.
b0: Null setting flag
Sets whether or not to write Null to PriorityArray.
• ON: Write
• OFF: Do not write
b1 to 5: Priority
Sets the priority for writing to PriorityArray. (1 to 16)
b0: Write flag
Sets whether or not to write the Value setting value to PriorityArray.
The write flag is enabled when OutOfService is set to OFF (FALSE).
• ON: Write
• OFF: Do not write
Stores the number of times PresentValue was updated. (0 to 32767)
b0: PresentValue
Stores the 32-bit data feedback value.
Stores the state size (maximum value of PresentValue). (0 to 4294967295)
*1
*2
*1