Update counter: The Ethernet module increments the counter every time a value is written to PriorityArray.
Range of the value: 01 to 655346553501 are repeatedly set.
(1) When the Ethernet module writes a value to the PriorityArray in the internal memory and calculates PresentValue, it updates the PresentValue in the buffer
memory, and increments the update counter.
(2) After the update counter has changed, the program reads the PresentValue in the buffer memory.
(3) Even when the value of PresentValue or the content of PriorityArray does not change, the Ethernet module increments the update counter when a value is
written to PriorityArray.
Therefore, it can be detected that there has been an update.
(4) Even when the program reads the PresentValue in the buffer memory at any timing, the value is the latest value.