AnalogInput (AI) object

This object handles analog input.
Property list
The following table lists available properties for the AnalogInput object.
Additionally, the availability of reading/writing data from/to a BACnet device is shown in the following table.
R: Read-only, W: Read/Write
PropertyID
Property
36
EventState
75
ObjectIdentifier
77
ObjectName
79
ObjectType
81
OutOfService
85
PresentValue
103
Reliability
111
StatusFlags
117
Units
371
PropertyList
*1 Only ANSI/ASHRAE Standard 135-2016 and ANSI/ASHRAE Standard 135-2012 are supported.
Buffer memory format of the AnalogInput object
For the format of the properties assigned to the buffer memory, refer to the following.
Page 85 BACnet communication AnalogInput
Ethernet module operation
■Operation at startup
For the startup operation, refer to the following.
Page 22 Ethernet module operation
Setting using a program
For the setting using the program, refer to the following.
Page 26 Setting using a program
4 FUNCTIONS
34
4.2 BACnet Object Function
*1
Data type
Enumerated
BACnetObjectIdentifier
CharacterString
Enumerated
BOOLEAN
REAL
Enumerated
BitString
Enumerated
BACnetARRAY[N]ofBACnetPropertyIdenti
fier
R/W
Description
R
Indicates the event status.
R
Indicates the ID to identify the object.
R
Indicates the object name.
R
Indicates the object type.
W
Indicates whether the device is
disconnected from the physical input.
W
Indicates the current value of the input
being measured.
R
Indicates reliability.
R
Indicates the object status.
R
Indicates the unit.
R
Indicates the property list.