■Multi-state Input object setting
Item
Instance No.
Object Name
Number_Of_States
State_Text
■Multi-state Output object setting
Item
Instance No.
Object Name
Number_Of_States
State_Text
Relinquish_Default
6 PARAMETER SETTINGS
60
6.3 Basic Settings
Description
Set an instance number for the Multi-state Input object. (The same
value cannot be set in the Multi-state Input object.)
Set an object name for the Multi-state Input object. (The same
value cannot be set in a module.)
Set the state size.
Set the text for the state, separated by semicolons (;).
Description
Set an instance number for the Multi-state Output object.
(The same value cannot be set in the Multi-state Output object.)
Set an object name for the Multi-state Output object. (The same
value cannot be set in a module.)
Set the state size.
Set the text for the state, separated by semicolons (;).
Set the value that will be set when PriorityArray is all NULL.
Setting range
0 to 4194303
(Default: Empty)
16 one-byte alphanumeric
characters maximum
(Default: Empty)
1 to 4294967295
(Default: 1)
Within 256 characters
(Default: Empty)
Setting range
0 to 4194303
(Default: Empty)
16 one-byte alphanumeric
characters maximum
(Default: Empty)
1 to 4294967295
(Default: 1)
Within 256 characters
(Default: Empty)
1 to the value set to
Number_Of_States
(Default: 1)