Establishing The Screw Connection Of Ahu Parts - Trane CCE-Compact Series Installation Operation & Maintenance

Air handling unit
Table of Contents

Advertisement

Additionally, to the base frame, there are other possibilities for connecting AHU parts. These are
listed below, ranked by the execution priority.
CCE COMPACT:
1.
Easy Connection, see Figure 23 and Figure 24
2.
Connection angle, see Figure 25 up to Figure 27
Figure 23: Easy Connection
Figure 25: Hexagon bolt with locknut
M8x20
5.1.3

Establishing the screw connection of AHU parts

The exact alignment of the AHU parts and pulling together of the AHU parts as close as possible, as
described in chapter 5.1.1(Actions before the assembly of casing), are requirements for estab-
lishing screw connection.
The precisely aligned and parallel flanges are connected with the enclosed bolts. Initially, all bolts
are only loosely screwed as follows:
In the base frame profiles (Figure 28).
-
In the connection angles located in the upper corners of the AHU (Figure 29).
-
-
For roof AHUs in the roof flange.
After placing all the screws loosely, they shall be tightened - starting with the base frame – in two
stages.
V07-19.0
Figure 24: Connection via Easy Connection
Figure 26: Connection angle
Figure 27: Connection via connection angle
27/115