Bacnet Ip - Trane CCE-Compact Series Installation Operation & Maintenance

Air handling unit
Table of Contents

Advertisement

Parameter
Termination
Baud rate
MX info frame
Max master
General:
Software version
Device ID
Module
Diagnostics
Use default
Table 38: BACnet MS/TP configuration
22.2.3

BACnet IP

Parameter
State
Comm failure
BACnet:
Device name
Device ID
Port
Imperial unit
system
Unicode
Description
language
Security level
Alarm server ID
Alarm device ID1
Alarm device ID2
Alarm device ID3
Comm mapping
TCP/IP:
96/115
Value
Description
Enable the termination resistor of the bus line [Passive]
Baud rate setting [76800]
MX info frame setting [1]
Max master setting [18]
Module configuration/info
Display software version
Display device ID
Display module information
Display diagnostic information from the module
Active
Set back to the default settings
Value
Description
Display hardware state of the module
Display communication error
Passive
No communication error
Active
Communikation error
Configuration of the BACnet side
Device name setting [POL908_......]
Device ID setting [4194303]
Communication port setting [47808]
Use of imperial unit system [Passive]
Passive
Metric unit system
Active
Imperial unit system (inch, °F, ...)
Enable Unicode [Passive]
Description language setting for data point list [English]; do not change it!!
Security level setting [0]
Alarm server ID setting [1]
Alarm device ID1 setting [0]
Alarm device ID2 setting [0]
Alarm device ID3 setting [0]
Used mapping setting [16384 = COM1]; do not change it!!
IP-interface configuration
V07-19.0

Advertisement

Table of Contents
loading

Table of Contents