Trane CCE-Compact Series Installation Operation & Maintenance page 102

Air handling unit
Table of Contents

Advertisement

Description
Supply speed smoke fan
Supply speed fireman fan
Return speed smoke fan
Return speed fireman fan
Supply fan request value
Return fan request value
Supply fan request stage
0=-, 1=Off, 2=Stage 1, 3=Stage 2, 4=Stage 3
Return fan request stage
0=-, 1=Off, 2=Stage 1, 3=Stage 2, 4=Stage 3
Fan control with air flow control:
Supply airflow rate for Eco mode
Supply airflow rate for Comfort mode
Supply airflow rate for Night Setback mode
Return airflow rate for Eco mode
Return airflow rate for Comfort mode
Return airflow rate for Night Setback mode
Maximum supply airflow rate from air quality control
Maximum return airflow rate from air quality control
Maximum supply airflow rate from dehumidification
Maximum return airflow rate from dehumidification
Supply airflow rate – request from air quality control
102/115
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
R/W
Unit
Modbus
R/W
0.1 %
H90
R/W
0.1 %
H91
R/W
0.1 %
H109
R/W
0.1 %
H110
R
0.1 %
H34
R
0.1 %
H35
R
0..4
H36
R
0..4
H37
R32/W32
m³/h
H10
R32/W32
m³/h
H12
R32/W32
m³/h
H18
R32/W32
m³/h
H14
R32/W32
m³/h
H16
R32/W32
m³/h
H20
R32/W32
m³/h
H22
R32/W32
m³/h
H24
R32/W32
m³/h
H30
R32/W32
m³/h
H32
R32
m³/h
H106
BACnet
Set_SupplySpeedSmoke
Set_SupplySpeedFire
Set_ReturnSpeedSmoke
Set_ReturnSpeedFire
SupplyFanSpeed
ReturnFanSpeed
SupplyFanStage
ReturnFanStage
Set_SupplyFlowEco
Set_SupplyFlowCmf
Set_SupplyFlowNht
Set_ReturnFlowEco
Set_ReturnFlowCmf
Set_ReturnFlowNht
Set_SupplyFlowQAirMax
Set_ReturnFlowQAirMax
Set_SupplyFlowDeHumMax
Set_ReturnFlowDeHumMax
SupplyFlowQAir
LON
nviPress_Flow00
nviPress_Flow01
nviPress_Flow04
nviPress_Flow02
nviPress_Flow03
nviPress_Flow05
V07-19.0

Advertisement

Table of Contents
loading

Table of Contents