Parameter
Password
Modbus:
Modbus RTU:
State
Slave address
Baudrate
Parity
Stop bits
Response delay
Termination
Modbus TCP/IP:
State
Table 41: Modbus RTU/IP on controller
V07-19.0
Value
Description
Password for WebVisu
Displays hardware status of interface
Adjustment slave address [1]
Adjustment baudrate [9600]; 1200, 2400, 4800, 9600, 19200, 38400 Baud
Parity setpoint [None]
None
No parity
Even
Even parity
Odd
Odd parity
Adjustment quantity of stop bits [1]
1
1 Stop bit
2
2 Stop bit
Adjustment delay between master request and slave respond [0ms]
Activate
end resistion [Passive]
Off
No termination
On
Bus line terminated
Displays hardware status of interface
99/115