Exception Day(S) - Trane CCE-Compact Series Installation Operation & Maintenance

Air handling unit
Table of Contents

Advertisement

Attention:
If only an entry for switching on and none for switching off is entered, then the AHU runs till
midnight and then with the settings of the next day.
It must be entered at least one switching point per day; if all switching points are deleted, then
the default setting is entered automatically (7:00 Comfort, 18:00 Off)
If the AHU should remain off for a day, then at least one switching point for off has to be
entered; it is better not to change the times and to set only the modes to Off.
Setting for Mo..Fr
1: Time
Mode
2: Time
Mode
3: Time
Mode
4: Time
Mode
5: Time
Mode
6: Time
Mode
Table 24: Scheduler settings (day)
Saturday and Sunday has the default setting off (7:00 operating mode „Off", 18:00 „Off").
15.2.2

Exception day(s)

The scheduler also includes an exception calendar, which allows you to use a special program for
events, without reprogramming the scheduler for individual days. This program can be entered in
advance. The setting when the exception is valid, is made in the lines Period:Start and Period:End.
The following settings are possible:
only one day
enter a date in the line Period:Start, enter nothing in the line Period:End
V07-19.0
Montay
Present value
Day schedule
1: Time
Mode
2: Time
Mode
3: Time
Figure 98: Scheduler - weekday
Description
1st entry– time
1st entry – operating mode
2nd entry – time
2nd entry – operating mode
3rd entry – time
3rd entry – operating mode
4th entry – time
4th entry – operating mode
5th entry – time
5th entry – opterating mode
6th entry – time
6th entry – operating mode
1/14
Comfort
Passive
07:00
Comfort
18:00
Off
": "
Default
07:00
Comfort
18:00
Off
": "
-
": "
-
": "
-
": "
-
79/115

Advertisement

Table of Contents
loading