Trane CCE-Compact Series Installation Operation & Maintenance page 105

Air handling unit
Table of Contents

Advertisement

Description
Minimum supply air temperature
Maximum supply air temperature
Saturation temperature setpoint (low limit)
Heating temperature setpoint for Eco mode
Heating temperature setpoint for Comfort mode
Cooling temperature setpoint for Eco mode
Cooling temperature setpoint for Comfort mode
Night Setback setpoint (Return air or room temperature)
Release temperature Night cooling (Release=Outdoortemp.>
value)
Summer compensation – fresh air temperature startpoint
Summer compensation – fresh air temperature endpoint
Summer compensation – offset at endpoint
Summer compensation – current offset
Winter compensation – fresh air temperature startpoint
Winter compensation – fresh air temperature endpoint
Winter compensation – offset at endpoint
Winter compensation – current offset
Current controlled variable/temperature
V07-19.0
R/W
Unit
Modbus
R/W
0,1 °C
H41
R/W
0,1 °C
H42
R/W
0,1 °C
H43
R/W
0,1 °C
H45
R/W
0,1 °C
H46
R/W
0,1 °C
H47
R/W
0,1 °C
H48
R/W
0,1 °C
H59
R/W
0,1 °C
H112
R/W
0,1 °C
H50
R/W
0,1 °C
H51
R/W
0,1 °C
H52
R
0,1 °C
H53
R/W
0,1 °C
H55
R/W
0,1 °C
H56
R/W
0,1 °C
H57
R
0,1 °C
H58
R
0,1 °C
H60
BACnet
Set_MinSupplyTemp
Set_MaxSupplyTemp
Set_SatTemp
Set_HeatEco
{unoccupied_heat}
Set_HeatCmf
{occupied_heat}
Set_CoolEco
{unoccupied_cool}
Set_CoolCmf
{occupied_cool}
Set_NightPurge
Set_MinOutTempNight
Set_SumCompStart
Set_SumCompEnd
Set_SumCompDelta
SumCompVal
Set_WinCompStart
Set_WinCompEnd
Set_WinCompDelta
WinCompVal
CtrlTemp_act
LON
nviTemps
{standby_cool}
nviTemps
(standby_heat}
nviTemps
nviTemps
nviTemps
nviTemps
nvoTemp05
nvoTemp05
105/115

Advertisement

Table of Contents
loading

Table of Contents