Trane CCE-Compact Series Installation Operation & Maintenance page 104

Air handling unit
Table of Contents

Advertisement

Description
Fan control with duct pressure control:
Supply duct pressure for Eco mode
Supply duct pressure for Comfort mode
Supply duct pressure for Night Setback mode
Return air duct pressure for Eco mode
Return duct pressure for Comfort mode
Return duct pressure for Night Setback mode
Maximum duct pressure from air quality control
Maximum return duct pressure from air quality control
Maximum supply duct pressure from dehumidification
Maximum return duct pressure from dehumidification
Supply duct pressure – request from air quality control
Return duct pressure – request from air quality control
Supply duct pressure – request from dehumidification
Return duct pressure – request from dehumidification
Supply duct pressure – current setpoint
Return duct pressure – current setpoint
Temperature control:
Temperature control mode
0=Return air/supply air cascade, 1=Constant supply air,
2=Return air, 3=Room/supply air cascade, 4=Room
104/115
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
R/W
Unit
Modbus
R/W
Pa
H10
R/W
Pa
H12
R/W
Pa
H18
R/W
Pa
H14
R/W
Pa
H16
R/W
Pa
H20
R/W
Pa
H22
R/W
Pa
H24
R/W
Pa
H30
R/W
Pa
H32
R
Pa
H97
R
Pa
H108
R
Pa
H99
R
Pa
H96
R
Pa
H26
R
Pa
H28
R/W
0..4
H40
BACnet
Set_SupplyPressEco
Set_SupplyPressCmf
Set_SupplyPressNht
Set_ReturnPressEco
Set_ReturnPressCmf
Set_ReturnPressNht
Set_SupplyPressQAirMax
Set_ReturnPressQAirMax
Set_SupplyPressDeHumMax
Set_ReturnPressDeHumMax
SupplyPressQAir
RetunPressQAir
SupplyPressDeHum
RetunPressDeHum
SupplyPressSet
ReturnPressSet
Set_TempCtrlMode
LON
nviPress_Flow00
nviPress_Flow01
nviPress_Flow04
nviPress_Flow02
nviPress_Flow03
nviPress_Flow05
V07-19.0