Trane CCE-Compact Series Installation Operation & Maintenance page 98

Air handling unit
Table of Contents

Advertisement

Parameter
General:
Software version
Device ID
Module
Use default
Table 40: LON configuration
22.2.5
Modbus RTU/ IP controller interfaces
Directly on controller there are 2 communication ports available (1 for IP and 1 for RTU). The IP in-
terface you can use for Web-Application (within your network), where you can monitor the same sit-
uation like on the local HMI display.
Modbus RTU (on board) has no galvanic isolation and is just to use for building management; if
power measurement will be done over IP, connection to BMS is not possible!
The configuration is carried out in the menu Configuration
Parameter
IP-Config: (TCP-Port: 502)
IP
Mask
Gateway
DHCP
Name
MAC
Change settings
IP
Mask
Gateway
DHCP
100 Mbit
Link
User name
98/115
Value
Description
Module configuration/info
Display software version
Display device ID
Display module information
Active
Set back to the default settings
Value
Description
Display IP address of controller
Display subnet mask
Display gateway address
Display DHCP status (automatic reference of IP address from a DHCP
server)
Controller name
Display MAC address
Submenu IP configuration
Config of IP address of controller
Config of subnet mask (controller)
Config of gateway address (controller)
Config DHCP [Active]
Passive
Manual address config
Active
Automatic address config by DHCP server
Switch-over interface speed 10/100Mbps [Active]
Passive
Speed 10Mbps
Active
Speed 100Mbps
Activate IP interface [Active]
Passive
Interface deactivated (no communication)
Active
Interface activated
User name for WebVisu
Communication controller.
V07-19.0

Advertisement

Table of Contents
loading

Table of Contents