Trane CCE-Compact Series Installation Operation & Maintenance page 100

Air handling unit
Table of Contents

Advertisement

23 Data points AHU
Description
Measured values:
Outdoor- / fresh air temperature
Supply air temperature
Supply air humidity
Return air temperature
Return air humidity
Room temperature
Room unit
Saturation temperature
Return air quality CO2
Supply airflow rate
Return airflow rate
Supply air duct pressure
Return air duct pressure
Actual outdoor enthalpy
Actual supply enthalpy
Actual return enthalpy
Actual room enthalpy
Operating mode:
100/115
R/W
Unit
Modbus
R
0,1 °C
I1
R
0,1 °C
I2
R
0,1 %
I6
R
0,1 °C
I3
R
0,1 %
I7
R
0,1 °C
I22
R
0,1 °C
I4
R
ppm
I16
R32
m³/h
I17
R32
m³/h
I19
R
Pa
I8
R
Pa
I9
R
0.1 kJ/kg
I23
R
0.1 kJ/kg
I24
R
0.1 kJ/kg
I25
R
0.1kJ/kg
I27
BACnet
OutDoorTemp
SupplyTemp
SupplyHumidity
nvoHum00 [%]
ReturnTemp
ReturnHumidity
nvoHum01 [%]
RoomTemp
SaturationTemp
ReturnAirQuality
SupplyFlow
nvoFlow00 [l/s]
ReturnFlow
nvoFlow01 [l/s]
SupplyDuctPressure
ReturnDuctPressure
Act_OutEnth
Act_SuEnth
Act_EhEnth
Act_RoomEnth
LON
nvoTemp01
nvoTemp02
nvoTemp03
nvoTemp06
nvoTemp04
nvoPpm00
V07-19.0