Field-Supplied Duct Connection To Ahu Bottom Supply/Return Air Opening; Discharge Plenum Connections - Trane CSAA Installation, Operation And Maintenance Manual

Performance climate changer air handlers indoor and outdoor units sizes 3 to 120
Hide thumbs Also See for CSAA:
Table of Contents

Advertisement

Figure 122. Field-supplied duct connection to AHU bottom supply/return air opening
Typical Trane
air handler base
Field-supplied
rigid duct
Figure 123. Field-supplied duct connection details - curb
mount for outdoor units
Unit wall
Unit base
3-50-14 ga
6 inches
57-120-10 ga
3-120-10 ga
Roof curb
Building roofing and
structure may vary per job
CLCH-SVX07K-EN
Bottom supply/
return airflow
Typical Trane
air handler base
Supply opening
Unit floor
in floor
3-120-16 ga
1 in. flange
Gasket
Field-supplied
duct
Field-supplied
rigid duct
Figure 124. Field-supplied duct connection details - pier
mount for outdoor units
Unit wall
Unit floor
Unit base
3-50 - 3 inches
57-120 - 4 inches
Building roofing and
structure may vary per job

Discharge Plenum Connections

Discharge plenum sections are available with or without
openings. Sections with rectangular and round openings
have a framed opening that can be used to secure the duct
to the frames. If the duct is lined, it is important the
insulation does not obstruct the opening of the section.
For a discharge plenum with field-cut openings, attach the
duct to the side panel.
Component Installation
Supply opening
in floor
1 in. flange
Gasket
Field-supplied
duct
97