Trane CCE-Compact Series Installation Operation & Maintenance page 106

Air handling unit
Table of Contents

Advertisement

Description
Current heating setpoint
Current cooling setpoint
Current heating setpoint for saturation temperature (HR,
heating 1, cooling 1)
Current cooling setpoint for saturation temperature (HR,
heating 1, cooling 1)
Minimal temperature difference cascade control
Maximal temperature difference cascade control
Recirculation damper – Minimum fresh air damper position
(always valid)
Recirculation damper – Maximum fresh air damper position
control (always valid)
Recirculation damper (0=closed, 1=open)
Heating/Cooling battery actual request value
Heating/Cooling battery actual mode
0=Winter, 1=Summer
Heating battery 2/post heating battery – valve position
Heating battery 2/post heating battery – Auto start
temperature
Heating battery 2/post heating battery – Preheating active
Heating battery 1/pre heating battery – valve position
Heating battery 1/pre heating battery – pre heating active
Heating battery 1/pre heating battery – Auto start
temperature
Electric heating battery – power request
106/115
R/W
Unit
Modbus
R
0,1 °C
H61
R
0,1 °C
H62
R
0,1 °C
H63
R
0,1 °C
H64
R/W
0,1 °C
H8
R/W
0,1 °C
H9
R/W
0,1 %
H71
R/W
0,1 %
H72
R
0..1
H38
R
0.1 %
H76
R
0..1
H74
R
0,1 %
H75
R/W
0.1 °C
H77
R
0..1
H73
R
0,1 %
H80
R
0..1
H44
R/W
0.1 °C
H39
R
0,1 %
H85
BACnet
CtrlHeatSet_act
CtrlCoolSet_act
CtrlSatHeatSet_act
CtrlSatCoolSet_act
Setpoint_DiffMin
Setpoint_DiffMax
Set_CircDmpMinFreshAir
Set_CircDmpMaxFreshAir
CircDmp_DO
H/CBatt_ActReq
H/CBatt_ActMode
HeatBatt2_Valve
HBatt2_PumpAutoSrtTemp
HBatt2_PreheatAct
HeatBatt1_Valve
HeatBatt1_PreHeatAct
HBatt1_PumpAutoStrtTemp
EBatt_Req
LON
nvoPerc03
nvoPerc04
nvoPerc05
V07-19.0