Trane CCE-Compact Series Installation Operation & Maintenance page 108

Air handling unit
Table of Contents

Advertisement

Description
Humidifier – power
Dehumidification – power request for dehumidification
Air quality control:
CO2 – return air quality setpoint for Eco mode
CO2 – return air quality setpoint for Comfort mode
Minimum fresh air damper position (for air quality control)
Maximum fresh air damper position (for air quality control)
Air quality control request value
Humidity control mode
0=Return humidity, 1=Supply humidity, 2=Room humidity
Circulation damper dehumidification priority
0=Auto, 1=Fresh air, 2=Return air
Circulation damper actual dehumidification priority
0=Fresh air, 1=Return air
Other:
Alarm acknowledge (1=Acknowledge, automatic return to 0
after 2s)
108/115
R/W
Unit
Modbus
R
0,1 %
H140
R
0,1 %
H145
R/W
ppm
H165
R/W
ppm
H166
R/W
0,1 %
H169
R/W
0,1 %
H170
R
0.1 %
H78
R/W
0..2
H79
R/W
0..2
H81
R
0..1
H82
W
0..1
H220
BACnet
Humidifier_Req
Dehumidification
Set_CO2Eco
Set_CO2Cmf
Set_MinFreshAirQCtrl
Set_MaxFreshAirQCtrl
Act_AirQCtrlVal
Set_HumCtrlMode
Set_DmpDehumPrio
Act_DmpDehumPrio
Set_AlarmAck
LON
nvoPerc08
nviPpm00
[%]
V07-19.0