When grounding the device, leave a service loop in the grounding cable to ensure
that the grounding cable is the last cable to disconnect from the shelf if strain is placed on
the electrical cables.

Task 3: Connecting the Power Cables to the CTP2000 Platform

WARNING:
the device is turned off, and proper grounding wires are attached.
To connect power cables to the device:
1. Be sure you have completed
Connecting the Grounding Cable to the CTP Platform (CTP2056 Platform Only)" on page
WARNING:
of the DC power source installed at your site. Color code standards for DC wiring
do not exist. To ensure that the correct polarity is connected to the device power
units, confirm the connection of the power cables to the + (positive) and – (negative)
leads at the power source.
2. Remove the nuts and locking washers from the posts for the power input (A or B) using a small insulated
adjustable wrench.
3. Place one negative (neutral) cable lead on the post labeled –48 VDC.
4. Replace the locking washers and nuts, and tighten the nuts to secure the connection.
5. Place the other cable lead on the post labeled RTN.
6. Replace the locking washer and nut, and firmly tighten the nut to secure the connection.
7. Attach the opposite end of Power A's wire leads to the appropriate leads on your power source.
Before you begin this procedure, be sure the power source is turned off,
"Task 1: Turning Off All CTP Platform Power" on page 112
The wiring color code of the power cables depends on the color coding