Byte
Element
:
:
136
First slot of ET 200AL (slot
67)
137
Reserved
:
:
166
Last slot of ET 200AL (slot
82)
167
Reserved
* The server module must be present in the station option and must not be marked as empty slot (BU cover).
10.2.3
Control data record for an interface module
Slot assignment
The following table shows the possible slots for the various modules for an
ET 200SP interface module:
Table 10- 3
Slot assignment
Modules
Interface module
Station extension
BA-Send
ET 200SP I/O module
Server module
ET 200AL I/O module
Distributed I/O system
System Manual, 09/2019, A5E03576849-AJ
Possible slots
0
1
1 - 12
for IM 155-6 PN BA
1 - 30
for IM 155-6 PN HS
1 - 32
for IM 155-6 PN ST,
IM 155-6 DP HF
1 - 64
for IM 155-6 PN HF,
IM 155-6 PN/3 HF
1 - 13
for IM 155-6 PN BA
1 - 31
for IM 155-6 PN HS
1 - 33
for IM 155-6 PN ST,
IM 155-6 DP HF
1 - 65
for IM 155-6 PN HF,
IM 155-6 PN/3 HF
34 - 49 for IM 155-6 DP HF
66 - 81 for IM 155-6 PN ST,
IM 155-6 PN HF,
IM 155-6 PN/3 HF
Code
:
Slot assignment in the
station option
:
Slot assignment in the
station option
Comment
The interface module (slot 0) is not an element of the configu-
ration control, but instead controls this.
For mixed configuration with ET 200AL modules, BA-Send is
always on slot 1.
Downstream from the interface module
The server module completes the configuration of the
ET 200SP station after the last I/O module.
For mixed configuration with ET 200AL modules
Configuration control (option handling)
10.2 Creating the control data record
Explanation
:
Control element ET 200AL
Contains information on which ET 200AL
module is inserted in which slot.
The value that you need to enter in the
corresponding byte depends on the fol-
lowing rule:
If the module exists in the station
•
option, enter the slot number of the
module.
If the module does not exist in the
•
station option, enter 0.
175